Ambient conditions
Accuracy of entire device
Load check, current
• Pulse period
2 s; T
ON
40 ms
• Periodic protection circuit
for overcurrent
f = 0.5 Hz
LCD display: Err3 switching output K1, Err4 switching output K2
Scaling range
Analog output
Scaling can be freely selected within the measuring range
Behavior when leaving the scaling
area (underrange)
Analog output 0 to 20 mA, linear drop up to 0 mA
Analog output 4 to 20 mA, linear drop up to 3.8 mA
Analog output 0 to 10 V, linear drop up to 0 V
Behavior when leaving the scaling
area (overrange)
Analog output 0 to 20 mA, linear increase up to 20.5 mA
Analog output 4 to 20 mA, linear increase up to 20.5 mA
Analog output 0 to 10 V, linear increase up to 10.2 V
Switching output
• Switching point
Measuring range (
>
release point)
• Release point
Measuring range (
<
switching point)
• Attenuation
0.00 to 99.99 s
• Switch-on delay
0.00 to 99.99 s
Burden
4 to 20 mA
R
I
≥
(U
B
- 6.5 V) / 0.022 A
0 to 20 mA
R
I
≥
(U
B
- 6.5 V) / 0.022 A
0 to 10 V
R
≥
10 k
Ω
Admissible temperatures
Ambient temperature, display case
-25 to +75 °C
Ambient temperature
-50 °C; restricted function
only stationary use, risk of cable break, LCD display without function
Storage temperature
-40 to +85 °C
Admissible air humidity
• During operation
100 % including condensation on the device outer case
• In storage
90 % without condensation
Admissible mechanical load
Referring to basic type 902940/10 and 902940/30 with insertion length 100 mm
• Vibration resistance
10 g, 10 to 2000 Hz according to IEC 60068-2-6
• Shock resistance
50 g for 11 ms / 100 g for 1 ms according to IEC 60068-2-27
Electromagnetic compatibility
(Only with 4-pin connecting cable and grounded case)
• Interference emission
Class A according to EN EN 61326
• Interference immunity
Performance characteristic A according to EN 61326
Protection type
IP67 according to DIN EN 60529
Ambient temperature influence
≤ ±
(15 ppm/K × (measuring range end value + 200) + 50 ppm/K × configured measuring range) ×
Δϑ
Δϑ
= deviation of the ambient temperature from the reference temperature
Calibration/reference conditions
DC 24 V at 25 °C
±
5 °C (77 °F
±
9 °F)
Measured value
Tolerance
100 °C
0.60 K
150 °C
0.75 K
200 °C
1.00 K
450 °C
1.60 K