Capillary and temperature probe
Type
Scale limit value
Capillary
∅ 1.5 mm
Temperature sensor
Remarks
ATH.-SW-..
up to 200 °C
Copper (Cu)
Material No. Cu-DHP
Copper (Cu)
Material No. Cu-DHP
hard soldered
- -
up to 350 °C
Copper (Cu)
Material No. Cu-DHP
Stainless steel (CrNi)
hard soldered
- -
up to 350 °C
Stainless steel (CrNi)
Stainless steel (CrNi)
Material No. 1.4571
welded
against surcharge
up to 500 °C
Stainless steel (CrNi)
Stainless steel (CrNi)
Material No. 1.4571
welded
- -
Capillary length
standard 1000 mm, maximum 5000 mm
min. bending radius
of capillary
5 mm
Electrical data
Switching element
TW, STW (STB)
STB
Microswitch with change-over contact
Microswitch with N/C contact
and restart lock
maximum contact rating
AC 230 V +10%, 10 (2), cos
ϕ = 1 (0.6)
DC 230 V +10%, 0.25A
with hysteresis 1.5% and 2%
AC 230 V +10%, 6 (1.2) A, cos
ϕ = 1 (0.6)
Microswitch, gold-plated, extra code /702*
(*only with hysteresis 3%, 5%, and 7%)
AC / DC 24 V, 0.1 A
contact resistance 2.5...10 m
Ω
Contact reliability
To ensure high switching reliability, we recommend a minimum load of:
with silver contacts:
AC / DC = 24 V, 100 mA
for gold-plated contacts (extra code "702“):
AC / DC = 10 V, 5 mA
Operating data
Hysteresis in % of the control
/ limit value range
Switching function
with fluid-filled measuring system
Rated value
Possible process value
Remarks
TW
3
3 max. 5
serial
6
6 max. 8
on request
1.5
1 max. 2
Surcharge
with gas-filled measuring system
5
4 max. 8
serial
9
8 max. 12
on request
2
1.5 max. 2.5
Surcharge
with fluid-filled measuring system
STW (STB)
5
4 max. 6
serial
9
8 max. 11
on request
2
1 max. 3
Surcharge
with gas-filled measuring system
7
5 max. 12
serial
9
8 max. 16
on request
2
1.5 max. 3
Surcharge
Switching point accuracy in
% of the control / limit value
range
TW: in the upper third of the scale ± 1.5%, at scale beginning ± 6%
STB, STW (STB): in the upper third of the scale +0/-5%, at scale beginning +0/-10%