6 Instrument description

22

Enclosure pro-
tection

EN 60 529 - IP 65

Operating
medium

Water, oil, air, superheated steam

Time constant
t

0.632

Mode of opera-
tion

according to EN 60 730-1

TW,TB:

Type 2BL = automatic action with micro-disconnection in
operation, no auxiliary supply required.

STW:

Type 2BKL = automatic action with micro-disconnection in
operation, fail-safe.

STB:

Type 2BFKL = automatic action with micro-disconnection in
operation, fail-safe, reset only permissible by means of a tool.

Operating posi-
tion
(NL)

To DIN 16257, NL 0 — NL 90 (other NL on request)

Weight

approx. 1.2 kg

Capillary and
probe material

Min. bending
radius of the
capillary

5 mm

in water

in oil

in air / superheated

steam

 45 s

 60 s

 120 s

End of scale

Capillary

Probe

up to +200°C

copper, Mat. Ref. 2.0090
electro-tinned
1.5 mm diameter

copper, Mat. Ref. 2.0090
electro-tinned
brazed

up to +300°C

copper, Mat. Ref. 2.0090
electro-tinned
1.5 mm diameter

stainless steel,
Mat. Ref. 1.4571
brazed

up to +500°C

stainless steel,
Mat. Ref. 1.4571
1.5 mm diameter

stainless steel,
Mat. Ref. 1.4571
welded

up to +300°C

stainless steel,
Mat. Ref. 1.4571
1.5 mm diameter

stainless steel,
Mat. Ref. 1.4571
welded