beautypg.com

7 troubleshooting, Troubleshooting, Chapter – JUMO 709050 IPC IGBT Power Converter IPC 70/100A Operating Manual User Manual

Page 49

background image

02.08 [IGBT Power Converter 70/100A]

49

7 Troubleshooting

What is happening?

Cause / Remedy

Information

Green power LED does
not light up

- Voltage supply to control section not

connected

v Chapter 4 „Electrical

connection“

IPC is not producing any
output power although
green LED
Power is lit and a
setpoint value has been
provided.

- Voltage supply to power section not

connected

v Chapter 4.1 „Screw

connections in the
power section“

- Analog control input not connected

correctly

v Chapter 4.1.5

„Wiring of the screw
terminals“

- Switch positions for control input S 101/8

and 9 or S104 set incorrectly

v Chapter 5.5 „Control

inputs“

h Check switch for firing pulse inhibit

S 105

v Chapter 5.6 „Firing

pulse inhibit“

- Load break

- Load short circuit („current-limit“ LED is

lit)

h Check load and load connections

IPC is not producing any
output power although
green power LED is lit, a
setpoint value is set and
the load fail LED is lit.

- Load break

- Load short circuit („current-limit“ LED is

lit at the same time)

h Check load and load connections
- Safety cut-out in the power section

v Chapter 5.12

„Safety cut-out in
the power section“

fuse LED is lit

- Semiconductor fuse blown by

earth short in the power section/

h remedy wiring fault or earth short in the

load

v Chapter 4.1.4

„Replacing the two
semiconductor
fuses“

IPC is not producing any
output power although
green power LED is lit, a
setpoint value is set and
the overheat LED is lit.

- Switch off caused by overheating

(clogged or faulty fan)

h Check the fan and replace, if necessary

- Insufficient supply of fresh air

- Inlet air temperature > 35°C

h Ensure sufficient ventilation

v Chapter 3.3

„Ambient
conditions“