7 troubleshooting, Troubleshooting, Chapter – JUMO 709050 IPC IGBT Power Converter IPC 70/100A Operating Manual User Manual
Page 49

02.08 [IGBT Power Converter 70/100A]
49
7 Troubleshooting
What is happening?
Cause / Remedy
Information
Green power LED does
not light up
- Voltage supply to control section not
connected
IPC is not producing any
output power although
green LED
Power is lit and a
setpoint value has been
provided.
- Voltage supply to power section not
connected
connections in the
power section“
- Analog control input not connected
correctly
„Wiring of the screw
terminals“
- Switch positions for control input S 101/8
and 9 or S104 set incorrectly
h Check switch for firing pulse inhibit
S 105
- Load break
- Load short circuit („current-limit“ LED is
lit)
h Check load and load connections
IPC is not producing any
output power although
green power LED is lit, a
setpoint value is set and
the load fail LED is lit.
- Load break
- Load short circuit („current-limit“ LED is
lit at the same time)
h Check load and load connections
- Safety cut-out in the power section
„Safety cut-out in
the power section“
fuse LED is lit
- Semiconductor fuse blown by
earth short in the power section/
h remedy wiring fault or earth short in the
load
„Replacing the two
semiconductor
fuses“
IPC is not producing any
output power although
green power LED is lit, a
setpoint value is set and
the overheat LED is lit.
- Switch off caused by overheating
(clogged or faulty fan)
h Check the fan and replace, if necessary
- Insufficient supply of fresh air
- Inlet air temperature > 35°C
h Ensure sufficient ventilation