3 Installation

16

[IGBT Power Converter 70/100A] 02.08

Switch-on
sequence

The voltage supplies to the control section and to the power section must be
switched on simultaneously.

3.2 Filtering and interference suppression

System

Compliance with the EMC standards can only be achieved through additional
EMC measures.

These include:

- a supply filter in the voltage supply

- a shielded cable for the voltage supply (from the supply filter (load) to the

IPC)

- a shielded cable to the load

- Functional equipotential bonding

Compliance with the EMC standards must be tested for the overall system.

Construction

To keep interference emission through conducted and radiated interference
below the permissible levels defined in the pertinent EMC standards,
constructive measures must be taken in the installation and wiring stages in
addition to supply input filtering. Poor earth connection or shielding of the
EMC filter will reduce the effectiveness of the interference suppression
measures.

The following points should be noted in order to achieve good configuration
for EMC purposes:

h All metallic components of the converter or cabinet must be well bonded

for HF currents over a large surface area.

h The EMC filter should be installed close to the IPC, if possible, on a

common metal plate. Route cables for control inputs and signal cables as
far apart from each other as possible, and use shielded cables.

h If possible, do not route power cables in the same cable duct as control or

signal cables.

h The cable between the load and the IPC should be as short as possible and

not exceed 50 m.

Earthing

The base plate, the supply filter and the shielding of the supply cable must be
earthed to a star point using HF braiding.

Choosing
a suitable
cable

k If the cable between the filter and the IPC is longer than 300 mm, we

recommend to use a shielded cable with the shielding earthed at both
ends. Route cables inside the switch cabinet as close as possible to
grounded surfaces, otherwise they can act as antennae and radiate
interference.

H

Under no circumstances may the voltage supply to the control
section be switched on before the load voltage. This is especially
important when operating resistive loads that have a high hot/cold
resistance ratio.