6 technical data – JUMO 709050 IPC IGBT Power Converter IPC 70/100A Operating Manual User Manual
Page 46

6 Technical data
46
[IGBT Power Converter 70/100A] 02.08
Power loss P
tot
(W)
It occurs in the form of thermal discharge at the cooling body of the power
converter.
v Chapter 3.3 „Ambient conditions“
Control accuracy
The regulation will eliminate supply voltage variations within the tolerances range
(+15%/-20%) with an accuracy of
Ϯ
0.5
%
Electrical connection
Control leads via plug-in screw terminals for conductor cross-sections from
0.5 to 2.5mm
2
, in the power section via screw terminals 10 to 50mm
2
.
protection rating
IP 20 as per EN 60 529
Protection class
Protection class I, with isolated control circuitry for connection to SELV circuits
Permissible ambient
temperature range
5 … 40°C (3K3 as per EN 60721-3-3)
Permissible storage
temperature range
-10 … +70°C (1K3 as per EN 60 721-3-1)
Cooling
forced convection, maximum inlet air temperature 35°C
Climatic conditions
Rel. humidity
≤ 5 to 85 % annual average, no condensation
3K3 as per EN 60721
Installation position
vertical
Operating conditions
The converter is designed as a built-in device as per EN 50178
Pollution degree 2, overvoltage category Ü III
Test voltage
as per EN 50178
Creepage distances
Control section to load circuit
≥ 5.5 mm
Control section to housing
≥ 5.5 mm
The converter can be connected to SELV circuits.
SELV = Separate Extra Low Voltage (safe low voltage)
Earth leaking current
The earth leakage current of the IPC power converter used with an EMC filter in
the supply cable is less than 3 mA (excluding any leakage current in the load).
Housing
Metal housing
Weight
approx.
17 kgs