background image

JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14

36039 Fulda, Germany

Postal address:

36035 Fulda, Germany

Phone:

+49 661 6003-0

Fax:

+49 661 6003-607

E-mail:

[email protected]

Internet:

www.jumo.net

JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:

+44 1279 635262

E-mail:

[email protected]

Internet: www.jumo.co.uk

JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866

1-800-554-5866

Fax:

315-437-5860

E-mail:

[email protected]

Internet: www.jumousa.com

2013-05-07/00529107

Data Sheet 705010

Page 6/15

Measuring circuit monitoring

In the event of an error the outputs move to a defined status.

Digital inputs

Analog outputs

Per optional board (option slot 1 to 3)

Selectable output behavior in case of an error according to NAMUR recommendation NE 43 (for signal type 2 to 10 V and 4 to 20 mA).

Digital outputs

Standard version

Measuring element

Underrange

Overrange

Probe or lead short
circuit

Probe or lead break

Thermocouple

Is detected

Is detected

Is not detected

Is detected

RTD temperature probe

Is detected

Is detected

Is detected

Is detected

Voltage

2 to 10 V

Is detected

Is detected

Is detected

Is detected

0 to 10 V

Is detected

Is detected

Is not detected

Is not detected

0 to 1 V

Is detected

Is detected

Is not detected

Is not detected

Current

4 to 20 mA

Is detected

Is detected

Is detected

Is detected

0 to 20 mA

Is not detected

Is detected

Is not detected

Is not detected

Heater current

Is detected

Is detected

Is not detected

Is not detected

Resistance transmitter

Is detected

Is detected

Is not detected

Is detected

Resistance/potentiometer

Is detected

Is detected

Is detected

Is detected

Number (standard version)

2 (input 1 and 2)

Optional number (option slot 1 to 3)

6 (input 5 to 10)

Input signal

DC 0/24 V (Input 1: Counting input up to 10 kHz)
(PLC level; logical "0” = -3 to +5 V; logical "1” = +15 to +30 V)

1 analog output (configurable)
(Output 1 to 3)

Load resistance R

Load

Accuracy

Ambient temperature
influence

Voltage DC 0(2) to 10 V

 500 

 0.25 %

 150 ppm/K

Current DC 0(4) to 20 mA

 500 

 0.25 %

 150 ppm/K

2 relay outputs (N/O)

Switching capacity

3A at AC 230V resistive load
3A at DC 30V resistive load

Contact life

150,000 operations at rated load / 350,000 operations at 1 A

or

2 logic outputs (to control external solid-state relays)

Output signal

DC 0/15 V

Current

Max. 25 mA per output

(Output 3 and 4)