Data Sheet 705010
Page 6/15
Measuring circuit monitoring
In the event of an error the outputs move to a defined status.
Digital inputs
Analog outputs
Per optional board (option slot 1 to 3)
Selectable output behavior in case of an error according to NAMUR recommendation NE 43 (for signal type 2 to 10 V and 4 to 20 mA).
Digital outputs
Standard version
Measuring element
Underrange
Overrange
Probe or lead short
circuit
Probe or lead break
Thermocouple
Is detected
Is detected
Is not detected
Is detected
RTD temperature probe
Is detected
Is detected
Is detected
Is detected
Voltage
2 to 10 V
Is detected
Is detected
Is detected
Is detected
0 to 10 V
Is detected
Is detected
Is not detected
Is not detected
0 to 1 V
Is detected
Is detected
Is not detected
Is not detected
Current
4 to 20 mA
Is detected
Is detected
Is detected
Is detected
0 to 20 mA
Is not detected
Is detected
Is not detected
Is not detected
Heater current
Is detected
Is detected
Is not detected
Is not detected
Resistance transmitter
Is detected
Is detected
Is not detected
Is detected
Resistance/potentiometer
Is detected
Is detected
Is detected
Is detected
Number (standard version)
2 (input 1 and 2)
Optional number (option slot 1 to 3)
6 (input 5 to 10)
Input signal
DC 0/24 V (Input 1: Counting input up to 10 kHz)
(PLC level; logical "0” = -3 to +5 V; logical "1” = +15 to +30 V)
1 analog output (configurable)
(Output 1 to 3)
Load resistance R
Load
Accuracy
Ambient temperature
influence
Voltage DC 0(2) to 10 V
500
0.25 %
150 ppm/K
Current DC 0(4) to 20 mA
500
0.25 %
150 ppm/K
2 relay outputs (N/O)
Switching capacity
3A at AC 230V resistive load
3A at DC 30V resistive load
Contact life
150,000 operations at rated load / 350,000 operations at 1 A
or
2 logic outputs (to control external solid-state relays)
Output signal
DC 0/15 V
Current
Max. 25 mA per output
(Output 3 and 4)