beautypg.com

JUMO 705010 mTRON T - Multichannel Controller Module Data Sheet User Manual

Page 5

background image

JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14

36039 Fulda, Germany

Postal address:

36035 Fulda, Germany

Phone:

+49 661 6003-0

Fax:

+49 661 6003-607

E-mail:

[email protected]

Internet:

www.jumo.net

JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:

+44 1279 635262

E-mail:

[email protected]

Internet: www.jumo.co.uk

JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866

1-800-554-5866

Fax:

315-437-5860

E-mail:

[email protected]

Internet: www.jumousa.com

2013-05-07/00529107

Data Sheet 705010

Page 5/15

Standard signals

Pt50

GOST 6651-94

-200 to +1100 °C

50 ppm/K

2-wire circuit

 0.30 %

3-wire/4-wire circuit

 0.06 %

Pt100

GOST 6651-94

-200 to +850 °C

50 ppm/K

2-wire circuit

 0.15 %

3-wire/4-wire circuit

 0.05 %

Cu50

GOST 6651-94

-50 to +200 °C

200 ppm/K

2-wire circuit

 0.80 %

3-wire/4-wire circuit

 0.60 %

Cu100

GOST 6651-94

-50 to +200 °C

200 ppm/K

2-wire circuit

 0.80 %

3-wire/4-wire circuit

 0.50 %

KTY11-6

-50 to +150 °C

50 ppm/K

2-wire circuit

 1 %

3-wire/4-wire circuit

 0.24 %

Sensor lead resistance

Max. 30

 per lead for 3-wire and 4-wire circuit

Max. 10

 per lead for 2-wire circuit

Measuring current

Pt100 approx. 250

A, Pt500, and Pt1000 approx. 100 A; not constant

Lead compensation

Not required for 3-wire and 4-wire circuit. For a 2-wire circuit, lead compensation can
be set in the software by correcting the actual value.

a

The accuracy values refer to the maximum measuring range. Smaller measuring ranges lead to reduced linearization accuracy.

Designation

Measuring range

Measuring accuracy

a

a

The accuracy values refer to the maximum measuring range. Smaller measuring ranges lead to reduced linearization accuracy.

Ambient temperature
influence

Voltage

 0.05 %

100 ppm/K

Input resistance R

E

> 500 k

DC 0(2) to 10 V

Input resistance R

E

> 100 k

DC 0 to 1 V

Current (voltage drop

 2 V)

DC 0(4) to 20 mA

 0.05 %

100 ppm/K

Heater current

AC 0 to 50 mA

 1 %

100 ppm/K

Resistance transmitter

100

 to 4 k

 4 

100 ppm/K

Resistance/potentiometer

100

 to 4 k

 4 

100 ppm/K

Designation

Standard

Measuring range

Measuring accuracy

a

Ambient temperature
influence