INF HOLD
Displayed when DMX is disconnected and the systems predetermined DMX status hold (SH) time
is set for infinite (INF) hold. Refer to menu item “SH TIME” on page 25 for further details.
SCENE:XX
Displays the scene (1 to 20) that is currently activated. The colon in front of the scene number
flashed twice per second during fading. Refer to menu item “SCENEMOD” on page 28 for further
details.
A-SCENE!
Displayed when the auxiliary input is triggered. Refer to menu item “AUX IN” on page 28 for
further details.
FIRE!!!
Displayed when the fire alarm input is triggered. Refer to menu item “F-ALARM” on page 29 for
further details.
SECURITY
Displayed when the security alarm input is triggered. Refer to menu item “S-ALARM” on page 28
for further details.
EXT-TEMP
Displayed when one or both of the two external over-temperature inputs is triggered. When the
EXT-TEMP is triggered all dimmer outputs are disabled and the fans are turned on to full until
the external devices temperature drops to within specification. See Over-Temperature Input
information on page 14 for further details.
REM-TEMP
Displayed when the systems remote temperature sensor measures an over-temperature
condition of 185°F (85°C) or more. All dimmer outputs are disabled and the fans are turned on
to full until the temperature cools down to 178°F (81°C) or less. The “REM TEMP” feature is not
used with CD-3000 Series retrofit systems. See menu item “REM TEMP” to view the current
remote temperature.
CTL-TEMP
Displayed when the microcontroller senses an internal over-temperature condition of 185°F
(85°C) or more. All dimmer outputs are disabled and the fans are turned on to full until the
temperature cools down to 178°F (81°C) or less. See menu item “CTL TEMP” to view the current
microcontroller temperature.
Ø ERROR!
Displayed when an error is sensed on any of the input power phases. A phase error can be
caused from an under-voltage of less than 100VAC, an over-voltage of greater than 130VAC, or if
a zero-cross phase reference is not detected.
RTC ERR!
Displayed when the system detects a runtime counter (RTC) error. This occurs when there is
an invalid hard-key code and the runtime counter is greater than 2160 hours (90 days). Refer to
menu item “HARD-KEY” on page 30 for further details.
LOCKED!!
Displayed when an attempt is made to access the system configuration menu items and the
programming switches are locked out. To toggle between “LOCKED!!” and “UNLOCKED” press
and hold down the “EXECUTE” and then “ESCAPE” switches at the same time for 4-5 seconds.
Also displayed when an attempt is made to access factory only setup menus.