Over-Temperature Input (Normally Closed)
• Terminate (OVERTEMP INPUT (NORMALLY CLOSED))
on J18 connector.
• Disables all dimmer outputs when contact/switch is opened.
• Controlled via a maintained contact/switch to +12V.
• Connects to OEM wiring in Strand CD80
®
Supervisor (SV) racks
via the power connector.
Over-Temperature Input (Normally Open) (TS1)
• Terminate (OVERTEMP INPUT (NORMALLY OPEN) (TS1))
on J18 connector.
• Disables all dimmer outputs when contact/switch is closed.
• Controlled via a maintained contact/switch to low-voltage
common (COMMON).
• Connects to OEM wiring in Strand CD80
®
Supervisor (SV) racks
via the power connector.
• Optionally connects to OEM wiring in Strand CD80
®
AMX
or Advanced Electronic (AE) racks.
Connect to TS1 located on the upper left-hand side of the dimmer rack.
Connect COM, also located on the upper left-hand side of the dimmer
rack, to COMMON on the CD-3000 Backplane.
Fire Alarm Input (Normally Open)
• Terminate on J18 connector.
• Triggers selected channels to turn on when contact/switch is closed.
• Controlled via a maintained contact/switch to low-voltage common (COM).
• Programmed in the “F-ALARM” menu. See page 29 for details.
Security Alarm Input (Normally Open)
• Terminate on J18 connector.
• Triggers selected channels to cycle on and off at a 1 Hertz rate when
contact/switch is closed.
• Controlled via a maintained contact/switch to low-voltage common (COM).
• Programmed in the “S-ALARM” menu. See page 28 for details.
Auxiliary Input (Normally Open)
• Terminate on J18 connector.
• Triggers 1 of 20 presets when contact/switch is closed.
• Controlled via a maintained contact/switch to low-voltage common (COM).
• Programmed in the “AUX IN” menu. See page 28 for details.
Open Collector Output
• Terminate on J18 connector.
• Sink up to 100mA.
• Trigger Solid State Relays (SSR) or other external devices.
• Controlled via DMX and/or Analog Input 4.
• Programmed in the “OC MODE” menu. See page 28 for details.