beautypg.com

INFICON HPG400-SD ATM to Ultra-High Vacuum Gauge (DeviceNet) User Manual

Page 23

background image

tira03e1-b (0310) BPG/HPG400-SDv1.cp

23

16 Bits are used as sensor warnings. Bit 8

… Bit 16 are mapped to the Exception

Detail Warning 5, Bit 0

… Bit 7 are mapped to the Exception Detail Warning 4.

Data Component

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Sensor Warning Byte 0

0

0

0

0

0

0

0

0

Sensor Warning Byte 1

0

0

0

0

Pressure
too high for
degas
(Only
BPG400-
SD).

0

0

0

The bit "Pressure too high for degas" will be set if the pressure is above
7.2×10

-6

mbar when a degas service is requested. The bit will be reset when the

pressure is below 7.2×10

-6

mbar (Only BPG400-SD).

Attribute

ID

Access

Rule

NV/

V

Name

DeviceNet
Data Type

Description of Attribute

Semantics of Values

3

Set / Con-

ditional:

Instance 1

NV

Data
Type

USINT

Determines the Data Type
of Value and all related
attributes as specified in
this table.

→ "Semantics" section below.
int

C3 hex [default]

float

CA hex

4

Get

NV

Data
Units

UINT

Determines the Units
context of Value and all
related attributes.

Supported Values:
Counts

1001

h

[default]

mbar

1308

h

Torr

1301

h

Pascal

1309

h

5

Get

V

Reading
Valid

BOOL

Indicates that the Value
attribute contains a valid
value.

0 = invalid
1 = valid

6

Get

V

Value

INT or speci-
fied by Data
Type

The value of the
Setpoint A (Setpoint B)
relay.

7

Get

V

Status

BYTE

Alarm and Warning State
of this object instance

→ "Semantics" section below.
Behavior as Trip Point LOW

A bit mapped byte which indicates the Alarm and Warning Exception status of the
object instance. The following definition applies:

Bit

Definition

0

High Alarm Exception:

0 = cleared

1 = set

1

Low Alarm Exception:

0 = cleared

1 = set

2

High Warning Exception: 0 = cleared

1 = set

3

Low Warning Exception: 0 = cleared

1 = set

4

Reserved

5

Reserved

6

Reserved

7

Reserved

If the pressure (attribute 6, instance 1 and 2) decreases below the Set Point value
(attribute 6, instance 21 and 22) an alarm or warning exception condition will be
generated. The hysteresis is set to 10%.
For example: A SET Point value of 100 will result in an exception condition being
set when the Value is below 100 and cleared when the Value increases above 110.

Sensor Warning

2.4.2.5 Instance Attributes of

Instance 21 / Setpoint A
(Instance 22 / Setpoint B)

Status

Set Points

This manual is related to the following products: