INFICON I/O1000 I/O module User Manual

Page 13

background image

Description

13

9 - RS485

Connection for RS-485

A: Active bus terminator
B: No bus terminator
C: Passive bus terminator

Electrical insulation (max. 60 V DC, 25 V AC against GND)

Connection plug arrangement

Information The bus terminator integrated in the I/O module (120 Ω) between D+

and D can be disabled via DIP switches S2-4.
The BUS address is 1.
BUS operation with more than two subscribers is not possible.

10 - 24V OUT

24V output

Connection plug arrangement

Information The I/O module is supplied with voltage by the MS module and requires

no separate power supply. The 24V output is not used for voltage
supply to the I/O module.

The 24V output of the I/O module can be used as an active signal for the PLC inputs
and outputs.

Fig: 5

RS-485 bus terminator

Pin

Name

1

Connect pull-up resistor (562 Ω against +5 V) with D+ if necessary

2

D+

3

D-

4

Connect pull-down (562 Ω against GND) with D- if necessary

5

COM

Pin

Name

+

+24 V

-

GND

1

2

3

4

5

562 Ω

120 Ω

562 Ω

DIP S2-4

RS485

D+

D-

+5 V

0 V