beautypg.com

Table 1 — physical data – Bryant DURAPAC PLUS 551B User Manual

Page 6

background image

6

Table 1 — Physical Data

LEGEND

Bhp — Brake Horsepower

UNIT 551B

090

102

120

150

NOMINAL CAPACITY (tons)

7

1

/

2

8

1

/

2

10

12

1

/

2

OPERATING WEIGHT (lb)

Unit

755

895

915

930

EconoMi$er IV

75

75

75

75

Perfect Humidity™ Dehumidification Package

44

51

51

51

Roof Curb

143

143

143

143

COMPRESSOR

Scroll

Quantity

2

2

2

2

Oil (oz) (each compressor)

53

53

50

60

REFRIGERANT TYPE

R-22

Expansion Device

Metering Device

Operating Charge (lb-oz)
Standard Unit

Circuit 1

7-10

9- 8

9-6

9-8

Circuit 2

8- 2

8-13

10-9

9-5

Unit With Perfect Humidity Dehumidification Package

Circuit 1

13-0

16-0

16-8

15-3

Circuit 2

13-6

16-8

17-8

16-6

CONDENSER FAN

Propeller Type

Quantity...Diameter (in.)

2...22

2...22

2...22

2...22

Nominal Cfm

6500

6500

7000

7000

Motor Hp...Rpm

1

/

4

...1100

1

/

4

...1100

1

/

4

...1100

1

/

4

...1100

Watts Input (Total)

650

650

650

650

CONDENSER COIL

High-Efficiency Enhanced Copper Tubes, Lanced Aluminum Fins

Rows...Fins/in.

2...17

2...17

2...17

2...17

Total Face Area (sq ft)

20.5

25.0

25.0

25.0

EVAPORATOR COIL

High Efficiency Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Face Split

Standard Unit

Rows...Fins/in.

3...15

4...15

4...15

4...15

Total Face Area (sq ft)

8.9

11.1

11.1

11.1

Unit with Perfect Humidity Dehumidification Package

Rows...Fins/in.

2...17

2...17

2...17

2...17

Total Face Area (sq ft)

6.3

8.4

8.4

8.4

EVAPORATOR FAN

Centrifugal Type, Belt Drive

Size (in.)

15 x 15

15 x 15

15 x 15

15 x 15

Nominal Cfm — Standard

3000

3400

4000

5000

Maximum Continuous Bhp

Standard

2.90

2.90

3.70

5.25

High Static

4.20

4.20

5.25

Motor Frame

56

56

56

56

Fan Rpm Range

Standard

840-1085

840-1085

860-1080

830-1130

High Static

860-1080

860-1080

830-1130

Motor Bearing Type

Ball

Ball

Ball

Ball

Maximum Fan Rpm

2100

2100

2100

2100

Motor Pulley Pitch Diameter A/B (in.)

Standard

3.4/4.4

3.4/4.4

4.0/5.0

2.8/3.8

High Static

4.0/5.0

4.0/5.0

2.8/3.8

Nominal Motor Shaft Diameter (in.)

7

/

8

7

/

8

7

/

8

7

/

8

Fan Pulley Pitch Diameter (in.)

Standard

7.0

7.0

8.0

5.8

High Static

8.0

8.0

5.8

Belt — Quantity...Type...Length (in.)

Standard

1...A...48

1...A...51

1...A...51

1...BX...46

High Static

1...A...55

1...A...55

1...BX...46

Pulley Center Line Distance (in.)

16.75-19.25

16.75-19.25

15.85-17.50

15.85-17.50

Speed Change per Full Turn of
Movable Pulley Flange (rpm)

Standard

50

50

45

60

High Static

60

60

60

Movable Pulley Maximum Full Turns
From Closed Position

Standard

5

5

5

6

High Static

5

5

6

Factory Setting — Full Turns Open

5

5

5

5

Factory Speed Setting (rpm)

Standard

840

840

862

887

High Static

860

860

887

Fan Shaft Diameter at Pulley (in.)

1

1

1

1

HIGH-PRESSURE SWITCH (psig)

Standard Compressor Internal Relief (Differential)

450 ± 50

Cutout

428

Reset (Auto.)

320

LOSS-OF-CHARGE/LOW-PRESSURE
SWITCH (Liquid Line) (psig)

Cutout

7 ± 3

Reset (Auto.)

22 ± 5

FREEZE-PROTECTION THERMOSTAT

Opens (F)

30 ± 5

Closes (F)

45 ± 5

OUTDOOR-AIR INLET SCREENS

Cleanable. Screen size and quantity varies by options selected.

RETURN-AIR FILTERS

Throwaway

Quantity...Size (in.)

4...16 x 20 x 2

4...16 x 20 x 2

4...20 x 20 x 2

4...20 x 20 x 2