Table 5 — Supply Air Sensor Temperature/Resistance

Values

The temperature sensor looks like an eyelet terminal with
wires running to it. The sensor is located in the “crimp end”
and is sealed from moisture.

Outdoor Air Lockout Sensor
The Economi$er IV is equipped with an ambient tempera-
ture lockout switch located in the outdoor airstream which is
used to lock out the compressors below a 42 F ambient tem-
perature. See Fig. 19.

G. EconoMi$er IV Control Modes
Determine the EconoMi$er IV control mode before set up of the
control. Some modes of operation may require different sensors.
Refer to Table 6. The EconoMi$er IV is supplied from the fac-
tory with a supply air temperature sensor and an outdoor air
temperature sensor. This allows for operation of the
EconoMi$er IV with outdoor air dry bulb changeover control.
Additional accessories can be added to allow for different
types of changeover control and operation of the EconoMi$er
IV and unit.

Table 6 — EconoMi$er IV Sensor Usage

*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on

many different base units. As such, these kits may contain parts that will
not be needed for installation.

†33ZCSENCO2 is an accessory CO

2

sensor.

**33ZCASPCO2 is an accessory aspirator box required for duct-mounted

applications.

††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2

and 33ZCASPCO2 accessories.

TEMPERATURE (F)

RESISTANCE (ohms)

–58

200,250

–40

100,680

–22

53,010

–4

29,091

14

16,590

32

9,795

50

5,970

68

3,747

77

3,000

86

2,416

104

1,597

122

1,080

140

746

158

525

176

376

185

321

194

274

212

203

230

153

248

116

257

102

266

89

284

70

302

55

APPLICATION

ECONOMI$ER IV WITH OUTDOOR AIR

DRY BULB SENSOR

Accessories Required

Outdoor Air Dry Bulb

None. The outdoor air dry bulb sensor

is factory installed.

Differential Dry Bulb

CRTEMPSN002A00*

Single Enthalpy

HH57AC078

Differential Enthalpy

HH57AC078

and

CRENTDIF004A00*

CO

2

for DCV Control

using a Wall-Mounted

CO

2

Sensor

33ZCSENCO2

CO

2

for DCV Control

using a Duct-Mounted

CO

2

Sensor

33ZCSENCO2†

and

33ZCASPCO2**

OR

CRCBDIOX005A00††

0

500

1000

1500

2000

2500

0.05

0.15

0.25

STATIC PRESSURE (in. wg)

FLOW IN CUBIC FEET

PER MINUTE (cfm)

Fig. 26 — Barometric Relief Flow Capacity

0

5

10

15

20

25

30

0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50

STATIC PRESSURE (in. wg)

FLOW IN CUBIC FEET

PER MINUTE (cfm)

Fig. 27 — Outdoor Air Damper Leakage

0

1000

2000

3000

4000

5000

6000

0.05 0.10 0.15 0.20 0.25 0.30 0.35

STATIC PRESSURE (in. wg)

FLOW IN CUBIC FEET

PER MINUTE (cfm)

Fig. 28 — Return Air Pressure Drop

SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
LOCATION

SUPPLY AIR
TEMPERATURE
SENSOR

Fig. 29 — Supply Air Sensor Location