background image

4

NOTES:

1. Place unit on curb as close as possible to the duct end.
2. Dimension in ( ) is in millimeters.
3. Hook rigging shackles through holes in base rail, as shown in

detail “A.” Holes in base rails are centered around the unit center
of gravity. Use wooden top skid when rigging to prevent rigging
straps from damaging unit.

4. Unit weights do not include economizer. See Table 1 for econo-

mizer weights.

5. Weights include base unit without the Perfect Humidity™ dehumid-

ification system. See Table 1 for additional unit operating weights
with the Perfect Humidity dehumidification system.

CAUTION:

All panels must be in place when rigging.

Fig. 6 — Rigging Details

551B

OPERATING

WEIGHT

A

B

C

lb

kg

in.

mm

in.

mm

in.

mm

090

755

343

77.42

1967

41.5

1054

42.12

1070

102

895

406

77.42

1967

41.5

1054

50.12

1273

120

915

415

77.42

1967

41.5

1054

50.12

1273

150

930

422

77.42

1967

41.5

1054

50.12

1273

MAXIMUM ALLOWABLE DIFFERENCE

(in.)

A-B

B-C

A-C

0.5

1.0

1.0

Fig. 3 — Unit Leveling Tolerances

DRAIN PLUG

HORIZONTAL
DRAIN OUTLET

NOTE: Drain plug is shown in factory-installed position.

Fig. 4 — Condensate Drain Location

NOTE: Trap should be deep enough to offset maximum unit static differ-
ence. A 4-in. trap is recommended.

Fig. 5 — Condensate Drain Piping Details