Table 12 — Evaporator-Fan Motor Data — High-Static Motors

LEGEND

BHP — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range

of the motors can be utilized with confidence. Using your fan motors up to the ratings shown in this
table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

Table 13 — Accessory/FIOP EconoMi$er IV Static Pressure* (in. wg)

LEGEND

*The static pressure must be added to external static pressure. The sum and the evaporator entering-

air cfm should be used in conjunction with the Fan Performance tables to determine indoor blower
rpm and watts.

Table 14 — Accessory/FIOP Electric Heaters Static Pressure (in. wg)

LEGEND

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should

be used in conjunction with the Fan Performance tables to determine indoor blower rpm and watts.

GENERAL FAN PERFORMANCE NOTES

1. Extensive motor and electrical testing on these units ensures that

the full range of the motor can be utilized with confidence. Using
fan motors up to the ratings shown will not result in nuisance trip-
ping or premature motor failure. Unit warranty will not be affected.
For additional information on motor performance refer to Evapora-
tor-Fan Motor Data, Tables 11 and 12.

2. Values include losses for filters, unit casing, and wet coils. See

Tables 13 and 14 and Fig. 36 for accessory/FIOP static pressure
information.

3. Use of a field-supplied motor may affect wire sizing. Contact

Bryant representative to verify.

4. Interpolation is permissible. Do not extrapolate.

UNIT

5551B

UNIT

PHASE

MAXIMUM

CONTINUOUS BHP*

MAXIMUM

OPERATING WATTS*

UNIT VOLTAGE

MAXIMUM

AMP DRAW

090,102

Three

4.20

3775

208/230

12.2

460

5.5

575

5.5

120

Three

5.25

4400

208/230

17.3

460

8.5

575

8.5

COMPONENT

CFM

2250

2500

2750

3000

3250

3500

3750

4000

4250

4500

4750

5000

5250

6250

Vertical EconoMi$er IV

0.06

0.075

0.09

0.115

0.13

0.15

0.17

0.195

0.22

0.25

0.285

0.325

0.36

Horizontal EconoMi$er IV

0.1

0.125

0.15

0.18

0.21

0.25

0.275

0.3

0.34

0.388

FIOP — Factory-Installed Option

COMPONENT

CFM

2200

2500

3000

3500

4000

4500

5000

5500

6000

1 Heater Module

0.02

0.03

0.05

0.065

0.08

0.10

0.12

0.14

0.155

2 Heater Modules

0.03

0.05

0.07

0.09

0.12

0.14

0.16

0.19

0.21

FIOP — Factory-Installed Option