Indoor Air Quality (IAQ) Sensor Input
The IAQ input can be used for demand control ventilation
control based on the level of CO

2

measured in the space or

return air duct.

Mount the accessory IAQ sensor according to manufacturer
specifications. The IAQ sensor should be wired to the AQ and

AQ1 terminals of the controller. Adjust the DCV potentiome-
ters to correspond to the DCV voltage output of the indoor air
quality sensor at the user-determined set point. See Fig. 35.

If a separate field-supplied transformer is used to power the
IAQ sensor, the sensor must not be grounded or the
EconoMi$er IV control board will be damaged.

CONTROL

CURVE

A
B
C
D

CONTROL POINT

APPROX. °F (°C)

AT 50% RH

73 (23)
70 (21)
67 (19)
63 (17)

12

14

1

6

18

20

2

2

24

26

28

30

32

34

36

38

40

42

44

46

90

10

0

80

70

60

50

40

30

20

10

ENT

HA

LP

Y—

BTU

P

ER

PO

UN

D DR

Y A

IR

85

(29)

90

(32)

95

(35)

100

(38)

105

(41)

110

(43)

35

(2)

35

(2)

40

(4)

40

(4)

105

(41)

110

(43)

45

(7)

45

(7)

50

(10)

50

(10)

55

(13)

55

(13)

60

(16)

60

(16)

65

(18)

65

(18)

70

(21)

70

(21)

75

(24)

75

(24)

80

(27)

80

(27)

85

(29)

90

(32)

95

(35)

100

(38)

APPROXIMATE DRY BULB TEMPERATURE— °F (°C)

A

A

B

B

C

C

D

D

RELA

TIVE HUM

IDITY

(%

)

HIGH LIMIT
CURVE

Fig. 33 — Enthalpy Changeover Set Points

TR1

24 Vac

COM

TR

24

Vac

HOT

1

2

3

4

5

EF

EF1

+

_

P1

T1

P

T

N

EXH

2V

10V

EXH

Set

Set

2V

10V

2V

10V

DCV

DCV

Free
Cool

B

C

A

D

SO+

SR+

SR

SO

AQ1

AQ

DCV

Min
Pos

Open

Max

N1

0

1000

2000

3000

4000

5000

6000

2

3

4

5

6

7

8

800 ppm

900 ppm

1000 ppm

1100 ppm

RANGE CONFIGURA

TION (ppm)

DAMPER VOLTAGE FOR MAX VENTILATION RATE

CO SENSOR MAX RANGE SETTING

2

Fig. 34 — EconoMi$er IV Control

Fig. 35 — CO

2

Sensor Maximum Range Setting