beautypg.com

Bryant DURAPAC PLUS 551B User Manual

Page 41

background image

41

Table 29 — Perfect Humidity™ Dehumidification System Sequence of Operation

and System Response — Dual Compressor Units

LEGEND

NOTE: On a thermostat call for W1, all cooling and dehumidification will be off.

F. Units With Power Exhaust

When the outdoor-air damper is modulated open, the two
end switches located in the actuator are tripped. The factory
settings are: switch no. 1 will close at 30% outdoor air;
switch no. 2 will close at 70% outdoor-air. Both switches are
field adjustable. As the outdoor-air damper opens, switch no.
1 closes, energizing a double-pole relay that starts fan no. 1.
As the outdoor-air damper continues to open, switch no. 2
will close, energizing a double-pole relay that starts fan no.
2. When the outdoor-air damper closes to a point below the
fan start points (30% fan no. 1, 70% fan no. 2), the respective
fan will be deenergized.

SERVICE

I. CLEANING

Inspect unit interior at the beginning of each heating and
cooling season or as operating conditions require.

A. Evaporator Coil

1. Turn unit power off and install lockout tag. Remove

evaporator coil access panel.

2. If EconoMi$er IV or accessory two-position damper is

installed, remove economizer or two-position damper
by disconnecting EconoMi$er IV plug and removing
mounting screws.

3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dish-

washer detergent in a pressurized spray canister.
Wash both sides of coil and flush with clean water.
For best results, back-flush toward return-air section
to remove foreign material.

5. Flush condensate pan after completion.
6. Reinstall economizer or two-position damper and filters.
7. Reconnect wiring.
8. Replace access panels.

B. Condenser Coils

Inspect coils monthly. Clean condenser coils annually, and as
required by location and outdoor-air conditions.

Clean 2-row coils as follows:

1. Turn off unit power and install lockout tag.
2. Remove top panel screws on condenser end of unit.

3. Remove condenser coil corner post. See Fig. 43. To

hold top panel open, place coil corner post between
top panel and center post. See Fig. 44.

4. Remove device holding coil sections together at

return end of condenser coil. Carefully separate the
outer coil section 3 to 4 in. from the inner coil section.
See Fig. 45.

5. Use a water hose or other suitable equipment to flush

down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in
the normal manner.

6. Secure the sections together. Reposition the coil sec-

tions, and remove the coil corner post from between
the top panel and center post. Install the coil corner
post and coil center post, and replace all screws.

THERMOSTAT

INPUT

ECONOMIZER FUNCTION

551B UNIT OPERATION

First Stage

Second Stage

H

Y1

Y2

OAT < Economizer

Set Point

Economizer

Compressor

1

Subcooling

Mode

Hot Gas

Reheat Mode

Compressor

2

Subcooling

Mode

Hot Gas

Reheat Mode

Off

Unit Operates Under Normal Sequence of Operation

On

On

On

No

Off

On

Yes

No

On

Yes

No

On

On

Off

No

Off

On

Yes

No

On

No

Yes

On

On

On

Yes

On

On

Yes

No

On

No

Yes

On

On

Off

Yes

On

On

No

Yes

On

No

Yes

On

Off

Off

No

Off

On

No

Yes

On

No

Yes

OAT

Outdoor Air Temperature

CAUTION: When servicing unit, shut off all elec-

trical power to unit to avoid shock hazard or injury
from rotating parts.

Fig. 43 — Cleaning Condenser Coil

Fig. 44 — Propping Up Top Panel