Operating Instructions Safety Switch CES-AH-C03-AH-SM

12

Connection example

Within the device, the shutdown of the two outputs LA and LB is dual-channel. As

such, each of the outputs represents a separate safety output.

1) Load, e.g. valve coil, DC motor, Ohmic load etc.

2) In case of inductive loads, it is imperative free-wheeling diodes are used to protect the outputs on the safety switch.

Figure 2: Connection example with start button and feedback loop

Attention!

Ì

A short circuit between the cables on the safety outputs LA and LB and an-
other cable must be prevented.

Ì

In certain circumstances, a failure exclusion as per EN 13849-1, section 7.3
can be applied, see also EN 13849-2, section D.5.2.

Ì

The CES-AH represents a subsystem as per EN 13849-1 and complies with
PL d. To integrate the switch in a category 3 structure, it is necessary to
monitor the downstream load (the feedback loop must be monitored).

Ì

This example shows only an excerpt that is relevant for connection of the
CES-AH system. The example illustrated here does not show complete
system planning. The user is responsible for safe integration in the overall
system.