30
SYSTEM SPECIFICATIONS
7400 EXM Monitor
Max Flow Rating
2500 GPM (9463 LPM)
Max Operating Pressure
500 PSI Limited Duty (34.5 BAR)
Inlet Size
4”-150# Flange, DN100
Outlet Size
3.5” Male NHT, 3.5” Male BSPP
Travel
V: -45° to +90° (-80° to +120° achievable)
H: L175° to R175°
Movement
Sealed Electric Motors
Stow Height
20”
Weight
52 Lbs.
Operating temperature range
-40°F to +185°F (-40°C to +85°C)
Environmental Rating
NEMA 4
Monitor Controller
Input power
12/24 VDC (11 VDC to 27 VDC)
Control Communication
CAN bus J1939
2.4 Ghz digital radio frequency (unlicensed)
Electrical Load
See Table 1 Below
Fuse Rating
40 AMPS (12V) & 20 AMPS (24V)
RF power output
Meets FCC part 15 requirements for license free operation
Operating temperature range
-40°F to +185°F (-40°C to +85°C)
Environmental Rating
NEMA 4
FCC ID
KQL-2510100
Motor
Left/Right
Up/Down
Nozzle
Run Current
10 A
10 A (25 A*)
2 A
Stall Current
70 A
70 A
10 A
Current Trip Point
20 A
20 A
4 A
Table 1: Motor Current Specifications
*With Foam Expansion Tube Utilization
Panel Mount Controller - 7010
Input power
12/24 VDC (11 VDC to 27 VDC)
Electrical Load
0.5 AMPS
Fuse Rating
1 AMPS (12V) & 0.5 AMPS (24V)
RF power output
Meets FCC part 15 requirements for license free operation
(Output if applicable)
Transmitter dimensions
7 17/32” x 3 19/32” X 1 1/8”
Transmitter weight
0.815 lbs.
Operating temperature range
-40°F to +185°F (-40°C to +85°C)
Environmental Rating
NEMA 4
FCC ID
KQL-2510100