Warning – Elkhart Brass Scorpion 7400 EXM Monitor User Manual
Page 24
24
F. Stow Position
The Stow Position is a preset position that can be used to bring the monitor into a position suitable for
when the system is powered off. A stow position must be within the allowed travel area defined by any
travel limits or keep-out zones, therefore it is recommended that travel limits and keep-out zones are
set before setting a stow position.
Move the monitor to the desired position while in normal operation; not in setup mode. If a travel
limit or keep-out zone boundary is met, move the discharge off the boundary a short distance.
Put the EXM system into Setup Mode (reference Part B of the Operating Instructions section)
Press the FOG and OSCILLATE buttons at the same time (rotate thumbwheel down for FOG on
Joystick)
This position will be the Stow Position when the system is brought out of Setup Mode
Simply press and hold the FOG and OSCILLATE buttons for three seconds to put the monitor into
the Stow Position while outside of Setup Mode (rotate thumbwheel down for FOG on Joystick)
Warning!
Water SHOULD NOT be flowing while stowing the monitor.
G. Motor Speed
The speed of both the horizontal and vertical motors can be changed from something different than
that set during configuration of the EXM system. The monitor’s horizontal and vertical motors can be
set to either Fast or Slow in one of four combinations.
Put the EXM system into the Setup Mode (reference Part B of the Operating Instructions section)
Press the OSCILLATE button to cycle through the various motor speed combinations
o
The horizontal, vertical, and nozzle LED’s on the monitor are used to show which motor
speed combination the monitor will be set at after Setup Mode is exited
o
All Yellow LED’s “OFF” places both motors in fast mode
o
One Yellow LED only “ON” indicates horizontal motor fast and vertical motor slow mode
o
Two Yellow LED’s only “ON” indicates horizontal motor slow and vertical motor fast mode
o
Three Yellow LED’s “ON” places both motors in slow mode
When the system is brought out of Setup Mode, the motor speeds will be changed to the
combination selected
H. Clear All Function
The Clear All Function allows the user to remove any Travel Limits, Keep-Out Zones, or Stow Positions
set while in Setup Mode. When the Clear All Function is used, it will remove all of the previously listed
operations. The Clear All Function will not affect calibration points, Motor Speed, or Preset valve
positions.
Put the EXM system into Setup Mode (reference Part B of the Operating Instructions section)
Press the OPEN and CLOSE buttons simultaneously
All set Travel Limits, Keep-Out Zones, and Stow Positions will be removed from the system