Det-Tronics X3300 Protect-IR Multispectrum IR Flame Detector User Manual
Page 4
![background image](/manuals/557723/4/background.png)
The X3300 is available in aluminum or stainless steel
and features multiple mounting options, including:
• Integral EEx d e aiming Swivel (for use with GRP EEx e
certified junction box)
• Direct to flexible conduit with the use of a Q9001
swivel mount
• Direct to junction box
• Direct to conduit elbow mount.
Table 2—Factory Configuration Options (Not Changeable in the Field)
Option
Available Configurations
Sensitivity
• Detects 1 square foot gasoline fire at 210 feet (very high
sensitivity) or 100 feet (medium sensitivity).
Optical Integrity (
oi)
*
Automatic
oi - Automatically checks internal circuitry and
cleanliness of viewing windows to ensure proper operation.
If a fault condition exists, the amber Fault LED lights.
• Manual
oi - Cleanliness of viewing windows test can be
manually initiated by closing an external switch that is elec-
trically connected between the
oi lead and circuit ground.
Warning:
Successful Manual
oi test results in fire alarm
relay activation and red Alarm LED lights.
• Internal circuitry is automatically tested independent of the
Manual
oi test
Fire Relay
Latching/Non-Latching
• Latching - Relay remains in “Fire” condition after fire has
been detected until X3300 power is cycled.
*
Non-latching - Relay remains in “Fire” condition only as long
as a fire is being detected.
Normally Energized/De-Energized
• Normally Energized - Fire relay is energized in non-alarm
(no fire) condition.
*
Normally De-Energized - Fire relay is de-energized in non-
alarm (no fire) condition.
Contacts Normally Open/Closed
*
Normally Open - Fire relay contacts are open in non-alarm
(no fire) condition.
• Normally Closed - Fire relay contacts are closed in non-
alarm (no fire) condition.
Fault Relay
Latching/Non-Latching
• Latching - Relay remains in “Fault” condition after fault has
been detected until X3300 power is cycled.
*
Non-latching - Relay remains in “Fault” condition only as
long as a fault is being detected.
Normally Energized
*
Normally Energized - Fault relay is energized with no fault
present.
Contacts Normally Open/Closed
*
Normally Open - Fault relay contacts are open when fault is
present.
• Normally Closed - Fault relay contacts are closed when
fault is present.
4 to 20 mA Output
• Current output level indicates detector status condition.
* Standard Configuration
2
Detector Status
LED Indicator
Power On/Normal Operation
Green
(no fault or fire alarm)
Fault Yellow
Fire (Alarm)
Red
Medium Sensitivity
Two Yellow Flashes
During Power-up
Very High Sensitivity
Four Yellow Flashes
During Power-up
Table 1—Detector Status Indicator