Det-Tronics X2200 UV Flame Detector with HART User Manual
Page 14
![background image](/manuals/557682/14/background.png)
95-8638
1.1
12
detector settings
This menu shows factory settings relating to relay operation, detector sensitivity and response.
1) uv mode
UV Mode: Standard or Arc.
2) Arc rejection
Detector ARC Rejection setting: Low, Medium, High, or Very High.
3) uv sensitivity
Detector UV sensitivity setting: Low, Medium, High, or Very High.
4) Auto oi enabled
Auto Oi Enabled. If (Y) an Oi test will be conducted periodically without manual
input.
5) Fire relay (nL/L)
Fire Relay: Latching (L) or Non-Latching (NL).
6) Fault relay (nL/L)
Fault Relay: Latching (L) or Non-Latching (NL).
7) Aux relay (nL/L)
Aux Relay: Latching (L) or Non-Latching (NL).
8) heater disabled
Heater Disabled. If (Y) the optics heater is not enabled to prevent condensation and
icing.
9) Aux Function
Aux function: Pre Alarm or UV Alarm.
10) Aux relay (ne/nde)
Aux Relay: Normally Energized (NE) or Normally De-Energized (NDE).
Device Info Menu
1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu
X2200 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu
Detector Settings
1) UV Mode
2) ARC Rejection
3) UV Sensitivity
4) Auto Oi Enabled
5) Fire Relay (NL/L)
6) Fault Relay (NL/L)
7) Aux Relay (NL/L)
8) Heater Disabled
9) Aux Function
10) Aux Relay (NE/NDE)