1
95-8528
11.1
INSTRUCTIONS
multispectrum IR flame Detector
with Pulse Output
X3301
Important
Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.
attEntIon
The X3301 includes the Automatic
oi ®
(Optical
Integrity) feature — a calibrated performance test
that is automatically performed once per minute
to verify complete detector operation capabilities.
testing with an external test lamp is not
approved or required.
DESCRIPTION
The X3301 with pulse/relay output is a multispectrum
infrared (IR) flame detector that is designed for use in
controller based systems. In addition to use in new
systems, it can serve as a direct field replacement
for Detector Electronics Corporation (Det-Tronics®)
controller based flame detectors that generate a pulse
output (not compatible with R7484 and R7409B/C).
When used as a field replacement, all operating features
of the current controller are retained in addition to gaining
the advanced features of the X3301 Flame Detector. In
typical applications, the four wire X3301 can utilize all
existing system wiring.
The X3301 contains three IR sensors and provides
unsurpassed detection of flames from light to heavy
hydrocarbon fuels combined with the highest degree of
false alarm rejection.
The detector has Division and Zone explosion-proof
ratings and is suitable for use in indoor and outdoor
applications. The X3301 housing is available in copper-
free aluminum or stainless steel, with NEMA/Type 4X and
IP66/IP67 rating.
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm or
fault conditions.
Microprocessor controlled heated optics increase
resistance to moisture and ice.
©
Detector Electronics Corporation 2013
Rev: 12/13