Det-Tronics X3301 Multispectrum IR Flame Detector with Pulse Output User Manual
Page 24
95-8528
11.1
22
FM approval and performance Report – Continued
RESpONSE ChaRaCTERISTICS
very high Sensitivity
Fuel
Size
Distance feet (m)
average Response Time (seconds)
n-Heptane
1 x 1 foot
210 (64)*
11
n-Heptane**
1 x 1 foot
210 (64)*
6
n-Heptane
1 x 1 foot
100 (30.5)
3
n-Heptane
6 in. x 6 in.
80 (24.4)
3
Isopropanol
6 in. x 6 in.
70 (21.3)
4
Diesel**
1 x 1 foot
150 (45.7)*
14
Ethanol
1 x 1 foot
210 (64)
11
Methanol
6 in. x 6 in.
40 (12.2)
3
Methanol
1 x 1 foot
150 (45.7)*
18
Methanol**
1 x 1 foot
150 (45.7)*
7
Methane
30 inch plume
100 (30.5)
3
JP-5**
1 x 1 foot
150 (45.7)*
2
JP-5**
2 x 2 feet
210 (64)*
4
JP-5**
2 x 2 feet
100 (30.5)
2
Office Paper 0.5 lb.
19" x 19" x 8"
100 (30.5)
4
Corrugated Panel
18" x 36"
100 (30.5)
8
* Outdoor test condition
** Pre-burn from ignition
Medium Sensitivity
Fuel
Size
Distance feet (m)
average Response Time (seconds)
n-Heptane
1 x 1 foot
100 (30.5)
12
n-Heptane
1 x 1 foot
50 (15.2)
2
Diesel**
1 x 1 foot
70 (21.3)
4
Ethanol
1 x 1 foot
85 (25.9)
13
Methanol
1 x 1 foot
70 (21.3)
10
Methane
30 inch plume
65 (19.8)
3
Methane
30 inch plume
55 (16.8)
2
JP-5**
2 x 2 feet
100 (30.5)
3
Office Paper 0.5 lb.
19" x 19" x 8"
50 (15.2)
6
Corrugated Panel
18" x 36"
50 (15.2)
2
** Pre-burn from ignition
Low Sensitivity
Fuel
Size
Distance feet (m)
average Response Time (seconds)
n-Heptane
1 x 1 foot
50 (15.2)
10
Methanol
1 x 1 foot
20 (6.1)
10
Methane
32 inch plume
15 (4.6)
9
T-Low Sensitivity
Fuel
Size
Distance feet (m)
average Response Time (seconds)
n-Heptane
1 x 1 foot
50 (15.2)
7
Methanol
1 x 1 foot
20 (6.1)
5
Methane
32 inch plume
15 (4.6)
4