Det-Tronics X3301 Multispectrum IR Flame Detector with Pulse Output User Manual
Page 27
25
95-8528
11.1
FM approval and performance Report – Continued
FaLSE aLaRM IMMUNITy
very high Sensitivity
False alarm Source
Distance
feet (m)
Modulated Response
Unmodulated Response
Sunlight, direct, reflected
—
No alarm
No alarm
Vibration
N/A
No alarm
N/A
Radio frequency interference
1 (0.3)
No alarm (keyed)
No alarm (steady)
Arc welding
40 (12.2)
No alarm
No alarm
6 kw heater
3 (0.9)
No alarm
No alarm
250 w vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w unshielded quartz halogen lamp
8 (2.4)
No alarm
No alarm
500 w shielded quartz halogen lamp
8 (2.4)
No alarm
No alarm
1500 w electric radiant heater
3 (0.9)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0.9)
No alarm
No alarm
Medium Sensitivity
False alarm Source
Distance
feet (m)
Modulated Response
Unmodulated Response
Sunlight, direct, reflected
—
No alarm
No alarm
Vibration
N/A
No alarm
N/A
Radio frequency interference
1 (0.3)
No alarm (keyed)
No alarm (steady)
Arc welding
10 (3)
No alarm
No alarm
6 kw heater
3 (0.9)
No alarm
No alarm
250 w vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w unshielded quartz halogen lamp
8 (2.4)
No alarm
No alarm
500 w shielded quartz halogen lamp
3 (0.9)
No alarm
No alarm
1500 w electric radiant heater
3 (0.9)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0.9)
No alarm
No alarm
T-Low Sensitivity
False alarm Source
Distance
feet (m)
Modulated Response
Unmodulated Response
Sunlight, direct, reflected
—
No alarm
No alarm
Vibration
—
No alarm
No alarm
Arc welding
5 (1.5)
No alarm
No alarm
6 kw heater
3 (0.9)
No alarm
No alarm
70 w sodium vapor
3 (0.9)
No alarm
No alarm
250 w vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w shielded quartz halogen lamp
3 (0.9)
No alarm
No alarm
1500 w electric radiant heater
3 (0.9)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0.9)
No alarm
No alarm
Low Sensitivity
False alarm Source
Distance
feet (m)
Modulated Response
Unmodulated Response
Sunlight, direct, reflected
—
No alarm
No alarm
Vibration
—
No alarm
No alarm
Radio frequency interference
N/A
No alarm
N/A
Arc welding
5 (1.5)
No alarm
No alarm
6 kw heater
3 (0.9)
No alarm
No alarm
250 w vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w shielded quartz halogen lamp
3 (0.9)
No alarm
No alarm
1500 w electric radiant heater
3 (0.9)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0.9)
No alarm
No alarm