Det-Tronics X5200 UVIR Flame Detector with HART User Manual
Page 14
95-8636
2.1
12
detector settings
This menu shows factory settings relating to relay operation, detector sensitivity and response.
1) uv mode
UV Mode: Standard or Arc.
2) ir mode
IR Mode: TDSA, Quick, or Both.
3) Arc rejection
Detector ARC Rejection setting: Low, Medium, High, or Very High.
4) uv sensitivity
Detector UV sensitivity setting: Low, Medium, High, or Very High.
5) ir sensitivity
Detector IR sensitivity setting: Low, Medium, High, or Very High.
6) Auto oi enabled
Auto Oi Enabled. If (Y) an Oi test will be conducted periodically without manual
input.
7) Fire relay (nL/L)
Fire Relay: Latching (L) or Non-Latching (NL).
8) Fault relay (nL/L)
Fault Relay: Latching (L) or Non-Latching (NL).
9) Aux relay (nL/L)
Aux Relay: Latching (L) or Non-Latching (NL).
10) heater disabled
Heater Disabled. If (Y) the optics heater is not enabled to prevent condensation and
icing.
11) Aux Function
Aux function: Pre Alarm, IR Alarm, UV Alarm, UV or IR Alarm, UV and IR Alarm.
12) Aux ir Function
Aux IR function: TDSA, Quick, or Both.
13) Aux relay (ne/nde)
Aux Relay: Normally Energized (NE) or Normally De-Energized (NDE).
Device Info Menu
1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu
X5200 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu
Detector Settings
1) UV Mode
2) IR Mode
3) ARC Rejection
4) UV Sensitivity
5) IR Sensitivity
6) Auto Oi Enabled
7) Fire Relay (NL/L)
8) Fault Relay (NL/L)
9) Aux Relay (NL/L)
10) Heater Disabled
11) Aux Function
12) Aux IR Function
13) Aux Relay (NE/NDE)