beautypg.com

Det-Tronics X9800 IR Flame Detector with Pulse Output User Manual

Page 9

background image

7

95-8555

5.1

pROTECTION agaINST MOISTURE DaMagE
It is important to take proper precautions during

installation to ensure that moisture will not come in

contact with the electrical connections or components

of the system. The integrity of the system regarding

moisture protection must be maintained for proper

operation and is the responsibility of the installer.

If conduit is used, we recommend installing drains,

according to local codes, at water collection points

to automatically drain accumulated moisture. It is

also recommended to install at least one breather,

according to local codes, at upper locations to provide

ventilation and allow water vapor to escape.

Conduit raceways should be inclined so that water

will flow to low points for drainage and will not collect

inside enclosures or on conduit seals. If this is not

possible, install conduit drains above the seals to

prevent the collection of water or install a drain loop

below the detector with a conduit drain at the lowest

point of the loop.

Conduit seals are not required for compliance with

explosion-proof installation requirements, but are

highly recommended to prevent water ingress in

outdoor applications. Units with M25 threads must use

an IP66/IP67 washer to prevent water ingress.

wIRINg pROCEDURE
wire Size and Type
The system should be wired according to local codes.

The wire size selected should be based on the number

of detectors connected, the supply voltage, and the

cable length. Typically 16 AWG or 2.5 mm

2

shielded

cable is recommended. Wires should be stripped

3/8 inch (9 mm). In some cases where the X9800 is

replacing existing pulse output detectors, the wiring

and power supplies may not be adequate. Consult the

factory for assistance.

Important

A minimum input voltage of 18 Vdc must be
present at the X9800.

The use of shielded cable is required to protect against

interference caused by EMI and RFI. When using

cables with shields, terminate the shields as shown in

Figures 6 through 10. Consult the factory if not using

shielded cable.

The “B” (pulse output) and “D” (

oi driver) leads from

each detector should be shielded from the “B” and “D”

leads of all other detectors in order to prevent false

alarms resulting from crosstalk between zones. It

is recommended that the “A” and “C” leads also be

shielded to provide maximum immunity to EMI/RFI.

(See Figures 6 to 10.)

In applications where the wiring cable is installed in

conduit, the conduit must not be used for wiring to other

electrical equipment.

If disconnection of power is required, separate disconnect

capability must be provided.

CaUtIon

Installation of the detector and wiring should be
performed only by qualified personnel.

Detector Mounting
Install the mounting arm assembly on a rigid surface.

The ideal installation surface should be free of vibration

and suitable to receive 3/8 inch (M9) bolts with a length

of at least 1 inch (25 mm). The surface must also have

sufficient capacity to hold the detector and mounting

arm weights (See “Specifications” section). Refer to the

Q9033 Mounting Arm manual (95-8686) for additional

mounting information. See Figure 3 for dimensions.

Detector wiring

Important

If installing an X9800 in place of an existing
detector, be sure to move the “A” lead (detector
power) at the controller from the +290 Vdc source
to the +24 Vdc source.

Do not apply 290 Vdc to

the X9800.

1. Make field connections following local ordinances

and guidelines in this manual.

Figure 4 shows the wiring terminal strip located

inside the detector’s integral junction box.

Figure 5 shows the wiring terminal identification for

the X9800 detector with pulse output.

Leave the shield open at the detector end and

permanently isolate it from accidental contact with

the case and/or other conductors. At the controller/

fire panel end, connect the shield and power minus

(–) to chassis (earth) ground either directly or

through a 0.47 µF 400 Volt non-polarized capacitor

(not supplied). (Refer to Figures 6 through 10.)