aPPENDIX a
FM appROVaL aND pERFORMaNCE REpORT
THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE FM APPROVAL:
• Explosion-proof for Class I, Div. 1, Groups B, C and D (T5) Hazardous (Classified) Locations per FM 3615.
• Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G (T5) Hazardous (Classified) Locations per FM 3615.
• Nonincendive for Class I, Div. 2, Groups A, B, C and D (T3) Hazardous (Classified) Locations per FM 3611.
• Nonincendive for Class II, Div. 2, Groups F and G (T3) Hazardous (Classified) Locations per FM 3611.
• Enclosure rating NEMA Type 4X per NEMA 250.
• Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
• Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).
Flameproof per ANSI/ISA 60079-0, -1, -7
for Class I, Zone 1 -
AEx d e IIC Gb; T6 (Tamb –40°C to +60°C); T5 (Tamb –40°C to +75°C)
AEx d IIC Gb; T6 (Tamb –40°C to +60°C); T5 (Tamb –40°C to +75°C)
for Zone 21 -
AEx tb T80°C
Tamb –40°C to +75°C
Degree of protection provided by Enclosure IP66/67, Hazardous Locations for use in the U.S.
The following accessories are FM approved for use with the X9800 Flame Detector:
part Number
Description
102740-002
Magnet
007739-001
Magnet and Extension Pole
007290-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
007290-002
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
011385-001
Q9033 Collar Attachment
The following performance criteria were verified:
aUTOMaTIC OpTICaL INTEgRITy TEST:
The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces
resulting in a loss of approximately 50% of its detection range, verifying that the detector performs a calibrated
Automatic Optical Integrity (oi) test for each sensor. Upon removal of the contamination, the detector fault was cleared
and the detector was verified to detect a fire.
MaNUaL OpTICaL INTEgRITy TEST:
The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally actuates the alarm
relay to verify output operation. If there is a 50% loss of its detection range, an alarm signal is not generated.
The oi test procedure, as described in the “Magnetic oi / Manual oi” section of this instruction manual, is the approved
external optical test method for this detector to verify end-to-end detector function. This test replaces the function and
need of a traditional external test lamp.