Symptom

Possible Cause

Next Step

Oven will

not control
at setpoint

High Limit set too low

Set the High Limit higher.

Protocol 3 controller
malfunction

Replace controller.

SSR malfunction

Replace SSR and/or check control output voltage.

Air friction of recirculation
fan

Open exhaust air vent. Unit will not control below
minimum operating temperature with vent closed.

Heater

does not

shut down

until temp.

reaches the

High Limit

setting


Protocol 3 controller
malfunction

Replace Protocol 3 controller.

SSR malfunction

Replace SSR.

Table 3. Troubleshooting with Control Panel Mounted Circuit Board.

If LED is…

Check…

1 LED

2LED

3 LED

Not Lit

Check Fuse Block 2F and 3F (Figure 14)

Lit

Not lit

Lit

Check High Limit

Check optional door switch, if appropriate

Lit

Lit

Lit

Check Fuse Block 1F and 4F (Figure 14)

Check SSR

Check heater

Check heater relays

Danger!

Table 3 lists troubleshooting steps that must be performed by a
qualified electrician or electrical technician trained on electrical
safety and the use of personal protective equipment.