3 Mounting
3.1 Mounting Options
This device is intended for integration into switch panels or switching cabinets. In order to allow for a safe
installation and operation (connector access), these switch panels or control desks must be accessible from the
back. The device can be integrated into switching cabinets with a wall thickness of 2..6 mm. We recommend a
minimum of 3 mm for correct installation with an IP65 front protection class.
Warning:
To avoid overheating in operation: The device must not be exposed to direct radiation by
sunlight or any other light or heat source.
If the device is integrated in a panel, casing or similar enclosures, you must ensure that no
heat accumulation builds up. The maximum permissible environmental temperature must
never be exceeded.
Devices including a data drive must only perpendicularly be integrated. Any deviation
must be agreed with ads‐tec.
The IP65 protection class is only achieved after correct installation.
If the device is delivered with a CD/DVD‐ROM drive, sufficient space (approx. 130mm)
must be provided on the left‐hand side if viewing the drive from the front, in order to
allow proper opening of the drive.
Note:
When selecting the enclosure for integration, the power dissipation total of the
system including that of all integrated PCBs must be taken into account. The
enclosure must be calculated in such a way that the maximum environmental
temperature is not exceeded in any case.