To achieve the minimum 'M' dimension,
this installation requires a spacer (by others)
between the fan and the wall.

If the wall is equal to or greater than the
minimum 'M' dimension, the fan can be
mounted directly to the wall.

WALL OPENING REQUIREMENTS
Wall opening size and the distance between propeller and damper are two important dimensions for fan installation.
Fans mounted to the wall require a different wall opening size than those mounted in collars or wall boxes. Propeller-
to-damper distance (M) is important to reduce turbulance at the damper which may lead to premature failure, and to
prevent the propeller blades from hitting the actuator on motorized damper units. Use general installation procedure
from page 4.

PROP

SIZE

PANEL SQ.

WALL OPENING (MIN.)

DAMPER SIZE

'M'

(MIN.)

SURFACE MOUNT

RECESS (IN WALL)

BSBP

BSDDP

BSBP

BSDDP

BSBP

BSDDP

BSBP

BSDDP

14

--

17.00

--

14.50

--

17.50

--

14 x 14

16.00

16

--

20.00

--

17.50

--

20.50

--

17 x 17

18

--

22.00

--

19.50

--

22.50

--

19 x 19

21

25.00

25.00

22.50

22.50

25.50

25.50

22 x 22

22 x 22

16.00

24

28.00

28.00

25.50

25.50

28.50

28.50

25 x 25

25 x 25

30

36.00

36.00

33.50

33.50

36.50

36.50

33 x 33

33 x 33

36

42.00

42.00

39.50

39.50

42.50

42.50

39 x 39

39 x 39

16.00

42

48.00

48.00

45.50

45.50

48.50

48.50

45 x 45

45 x 45

48

54.00

54.00

51.50

51.50

54.50

54.50

51 x 51

51 x 51

54

60.00

--

57.50

--

60.50

--

57 x 57

--

19.00

60

66.00

--

63.50

--

66.50

--

63 x 63

--

Panel Installation (without accessories) — BSBP & BSDDP