Check, Test & Start Procedure

WARNING

Electric shock hazard. Could cause severe injury or

death. Failure to bond the frame of this equipment

to the building electrical ground by use of the

grounding terminal provided or other acceptable

means may result in electrical shock. Disconnect

electric power before servicing equipment. Service

to be performed only by qualified personnel.

BEFORE START-UP: Disconnect power to this unit

before servicing the unit.

1. Check to verify that the propeller is free to rotate.
2. Verify that supply voltage on the line side of discon-

nect agrees with voltage on fan data plate and is

within the 10% utilization voltage.

3. Apply power to unit and check rotation of propeller

with the directional arrow on the unit.

WARNING: Rotation is critical. If allowed to operate

in the wrong direction, the motor will overload and

burn out.

WARNING: Especially check three-phase units for

rotation. For three-phase, rotation can be changed by

interchanging any two of the three line leads. If unit is

checked on temporary wiring, it should be rechecked

when permanently installed. Motor burn-out or tripped

overload protection devices are usually the result of

wrong rotation.

4.

Electrical Input Check: Perform check of fan ampere

draw and verify that motor nameplate amps are not

exceeded. Take into account the service factor range

if motor is nameplated above a 1.0 service factor.

5. Fan RPM should be checked and verified with a

tachometer.

Electrical Connection

1. Connect supply wiring to a disconnect switch.

Check the wiring diagrams on the motor for con-

nections.

2. The motor is factory set at the voltage marked on

the fan nameplate. Check the line voltage with the

nameplate voltage and wiring diagrams.

3. The main power wiring should be sized for the

ampacity shown on the dataplate. Size wires in

accordance with the ampacity tables in Article 310

of the National Electrical Code. If long wires are

required, it may be necessary to increase wire size

to prevent excessive voltage drop. Wires should be

sized for a maximum of 3% voltage drop.

CAUTION: Use copper conductors only.

CAUTION: Protect wiring from sharp edges. Leave

some slack in the line to prevent damage.

4. (Optional) Disconnect switches are not fused. The

power leads must be protected at the point of dis-

tribution in accordance with the fan dataplate.

5. On fans without a thermal protector integral to the

motor (refer to unit or motor dataplate to determine

if protector is present) a separate overload device

is required. Refer to Sections 430-32 of the N.E.C.

for sizing.

6. All units must be electrically grounded in accordance

with local codes or, in the absence of local codes,

with the latest edition of the National Electrical

Code (ANSI/NFPA 70).

A ground lug is provided as

standard in the unit terminal box. Size grounding

conductor in accordance with Table 250-95 of the

National Electrical Code.

DO NOT use the ground

lug for connecting a neutral conductor.

7. Supply voltage to the power ventilator should not

vary by more than 10% of the value indicated

on the unit dataplate. Phase unbalance must not

exceed 2%.

WARNING: Failure of motor due to operation on

improper line voltage or with excessive phase unbal-

ance constitutes product abuse and may cause

severe damage to the unit’s electrical components.