TABLE 37 – PULLEY ADJUSTMENT

UNIT

Motor/Drive Combo

Motor Pulley turns open

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

5

04

3

Phase

Medium Static

1175

1135

1094

1054

1013

973

932

892

851

811

770

High Static

1466

1423

1380

1337

1294

1251

1207

1164

1121

1078

1035

05

3

Phase

Medium Static

1303

1265

1226

1188

1150

1112

1073

1035

997

958

920

High Static

1639

1596

1553

1510

1467

1424

1380

1337

1294

1251

1208

06

3

Phase

Medium Static

1466

1423

1380

1337

1294

1251

1207

1164

1121

1078

1035

High Static

1687

1649

1610

1572

1533

1495

1457

1418

1380

1341

1303

07

3

Phase

Standard Static

747

721

695

670

644

618

592

566

541

515

489

Medium Static

949

927

906

884

863

841

819

798

776

755

733

High Static

1102

1083

1063

1044

1025

1006

986

967

948

928

909

08

3

Phase

Standard Static

733

712

690

669

647

626

604

583

561

540

518

Medium Static

936

911

887

862

838

813

788

764

739

715

690

High Static

1084

1059

1035

1010

986

961

936

912

887

863

838

09

3

Phase

Standard Static

733

712

690

669

647

626

604

583

561

540

518

Medium Static

936

911

887

862

838

813

788

764

739

715

690

High Static

1084

1059

1035

1010

986

961

936

912

887

863

838