beautypg.com

Curbs & weights dimensions j04 (cont.), Cb a d – Bryant PREFERRED 581J User Manual

Page 17

background image

17

CURBS & WEIGHTS DIMENSIONS -- 581J04--06 (cont.)

UNIT

STD. UNIT

WEIGHT

CORNER

WEIGHT (A)

CORNER

WEIGHT (B)

CORNER

WEIGHT (C)

CORNER

WEIGHT (D)

C.G.

HEIGHT

LBS. KG. LBS. KG. LBS. KG. LBS. KG. LBS. KG.

X

Y

Z

505

229

124

56

117

53

128

58

136

62

36 1/8 [918]

24 3/8 [619]

19 [483]

590

268

151

69

144

65

144

65

151

69

36 1/4 [921]

23 3/8 [594]

20 1/8 [511]

600

271

156

71

145

66

144

65

155

70

35 7/8 [911]

23 1/4 [591]

19 1/2 [495]

*- STANDARD UNIT WEIGHT IS WITH LOW GAS HEAT AND WITHOUT PACKAGING.

FOR OTHER OPTINS AND ACCESSORIES REFER TO THE PRODUCT DATA CATALOG.

X

Y

CORNER A

CORNER B

CORNER C

CORNER D

TOP

Z

581J-04A

581J-05A

581J-06A

C10379

Fig. 2 -- Dimensions 581J04--06

C

B

A

D

C08337

Fig. 3 -- Service Clearance

LOC

DIMENSION

CONDITION

A

48” (1219 mm)

Unit disconnect is mounted on panel

18” (457 mm)

No disconnect, convenience outlet option

18” (457 mm)

Recommended service clearance

12” (305 mm)

Minimum clearance

B

42” (1067 mm)

Surface behind servicer is grounded (e.g., metal, masonry wall)

36” (914 mm)

Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)

Special

Check for sources of flue products within 10---ft of unit fresh air intake hood

C

36” (914 mm)

Side condensate drain is used

18” (457 mm)

Minimum clearance

D

48” (1219 mm)

No flue discharge accessory installed, surface is combustible material

42” (1067 mm)

Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)

36” (914 mm)

Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)

Special

Check for adjacent units or building fresh air intakes within 10---ft of this unit’s flue outlet

581J