beautypg.com

Bryant PREFERRED 581J User Manual

Page 15

background image

15

TABLE 11 – PHYSICAL DATA

(HEATING)

7.5 -- 8.5 TONS

581J*08D

581J*09D

Gas Connection

# of Gas Valves

1

1

Nat. gas supply line press (in. w.g.)/(PSIG)

4 ---13 / 0.18 --- 0.47

4 ---13 / 0.18 --- 0.47

Propane supply line press (in. w.g.)/(PSIG)

11 ---13 / 0.40 --- 0.47

11 ---13 / 0.40 --- 0.47

Heat Anticipator Setting (Amps)

1st stage

0.14

0.14

2nd stage

0.14

0.14

Natural Gas, Propane Heat

# of stages / # of burners (total)

2 / 3

2 / 3

LO

W

Connection size

1/2” NPT

1/2” NPT

Rollout switch opens / closes

195 / 115

195 / 115

Temperature rise range (F)

20 --- 50

20 --- 50

# of stages / # of burners (total)

2 / 4

2 / 4

MED

Connection size

3/4” NPT

3/4” NPT

Rollout switch opens / closes

195 / 115

195 / 115

Temperature rise range (F)

35 --- 65

30 --- 65

# of stages / # of burners (total)

2 / 5

2 / 5

HI

G

H

Connection size

3/4” NPT

3/4” NPT

Rollout switch opens / closes

195 / 115

195 / 115

Temperature rise range (F)

45 --- 75

40 --- 75

581J