Class1 Intelli Tank level display with drip empty User Manual
Page 14
![background image](/manuals/546745/14/background.png)
Intelli-Tank Manual (106759)092204
– 14 –
Class 1
Condition
Evaluate
Bottom two LEDs
alternate flashing.
Unit fails self test,
LED 1 flashing.
Check transducer wiring. Ensure +5V at pin A, ground at pin B and
at least .4V at pin C (Signal).
Top two LEDs
alternate flashing.
Unit fails self test,
LED 1 on.
Check transducer wiring. Ensure +5V at pin A, ground at pin B and
no more than 4.8V at pin C (Signal).
Middle two LEDs
alternate flashing.
Perform self test. If it fails with LED 3 on replace unit.
Outer two LEDs
alternate flashing.
Try to recalibrate. If condition remains, check if transducer signal
voltage (pin C) changes as tank level increases. If it doesn’t,
replace transducer. If it does, verify depth of tank. It may be
impossible to calibrate a tank with a depth of less than 6 inches.
Bottom two and
Upper two LEDs
alternate flashing.
The unit is configured as a Remote. If it required to be a Master
then recalibrate. If the unit is required to be a Remote check Data
line (Pin 4) continuity and insure line is not grounded.
No LEDS on.
Check power (Pin 1) and ground (Pin 2) connection.
Master Tank level
display does not
change when actual
tank level is
changing.
Check transducer wiring. Ensure transducer signal voltage (Pin C)
is varying. If it does, check for same signal changes at Pin 6 of
tank level connector (if it is not the same repair wiring). If signal is
good at both locations try re-calibrating.
Remote Tank level
display does not
follow Master
display.
Perform self test. If self test is good, check pin 4 (data line) for
continuity and insure it is not shorted to ground or power. Insure
data line is not routed near noisy power or RF sources.
Unit fails self test,
LED 2 on.
Check pin 4 (data line) for continuity and insure it is not shorted to
ground or power.
No passwords are
accepted.
If the display issues the “wave off” after entering a password,
insure the unit is installed upright. During power-up the display
should cycle on each LED individually starting with the bottom
LED.
Check that the left and right magnetic switches are recognized by
activating each switch and verifying that the associated LEDs
illuminate.