beautypg.com

Caution, Warning, Step 6 — provide for condensate disposal – Bryant 604D--A User Manual

Page 9: Step 7 — install electrical connections

background image

9

Step 6 — Provide for Condensate Disposal

NOTE: Ensure that condensate--water disposal methods comply
with local codes, restrictions, and practices.
The 604D----A units dispose of condensate through a 3/4 in. NPT

female fitting that exits on the compressor end of the unit.

Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in ground

level installations. Install a field--supplied 2--in. (51 mm)
condensate trap at end of condensate connection to ensure proper

drainage. Make sure that the outlet of the trap is at least 1 in. (25

mm) lower than the drain--pan condensate connection to prevent
the pan from overflowing. Prime the trap with water. When using a

gravel apron, make sure it slopes away from the unit.
If the installation requires draining the condensate water away from

the unit, install a field--supplied 2 --in. (51mm) trap at the
condensate connection to ensure proper drainage. Condensate trap

is available as an accessory or is field--supplied. Make sure that the

outlet of the trap is at least 1 in. (25 mm) lower than the unit
drain--pan condensate connection to prevent the pan from

overflowing. Connect a drain trough using a minimum of
field--supplied 3/4--in. PVC or field--supplied 3/4--in. copper pipe

at outlet end of the 2--in. (51 mm) trap. (See Fig. 10) Do not

undersize the tube. Pitch the drain trough downward at a slope of at
least 1 in. (25 mm) every 10 ft (3 m) of horizontal run. Be sure to

check the drain trough for leaks. Prime the trap at the beginning of
the cooling season start--up.

Step 7 — Install Electrical Connections

UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit

being installed.

1. Make all electrical connections in accordance with NEC

NFPA 70 (latest edition) and local electrical codes

governing such wiring. In Canada, all electrical
connections must be in accordance with CSA standard

C22.1 Canadian Electrical Code Part 1 and applicable
local codes. Refer to unit wiring diagram.

2. Use only copper conductor for connections between

field--supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.

3. Be sure that high--voltage power to unit is within

operating voltage range indicated on unit rating plate. On
3--phase units, ensure phases are balanced within 2

percent. Consult local power company for correction of
improper voltage and/or phase imbalance.

4. Do not damage internal components when drilling

through any panel to mount electrical hardware, conduit,
etc.

!

CAUTION

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury

or death.
The unit cabinet must have an uninterrupted, unbroken

electrical ground. This ground may consist of an electrical

wire connected to the unit ground screw in the control

compartment, or conduit approved for electrical ground when

installed in accordance with NEC,NFPA 70 National Fire

Protection Association (latest edition) (in Canada, Canadian

Electrical Code CSA C22.1) and local electrical codes.

!

WARNING

High--Voltage Connections

The unit must have a separate electrical service with a

field--supplied, waterproof disconnect switch mounted at, or within
sight from the unit. Refer to the unit rating plate, NEC and local

codes for maximum fuse/circuit breaker size and minimum circuit
amps (ampacity) for wire sizing.
The field--supplied disconnect may be mounted on the unit over
the high--voltage inlet hole when the standard power and

low--voltage entry points are used. See Fig. 2 and 3 for acceptable

location. Remove high voltage knockout.
See unit wiring label (Fig. 11--13) and Fig. 9 for reference when

making high voltage connections. Proceed as follows to complete
the high--voltage connections to the unit.
Single phase units:

1. Run the high--voltage (L1, L2) and ground lead into the

control box.

2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side

of the contactor.

POWER
SUPPLY

FIELD-SUPPLIED
FUSED DISCONNECT

HIGH VOLTAGE
POWER LEADS
(SEE UNIT WIRING
LABEL)

EQUIP GR

CONTROL BOX

LOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL

)

W1

Y

G

R

C

WHT(W1)

YEL(Y)

GRN(G)

RED(R)

BRN(C)

THERMOSTAT
(TYPICAL)

ORN(O)

3-PHASE SHOWN
1-PHASE USES
TWO POWER
LEADS

W2

VIO (W2)

O

SPLICE BOX

DH

BLU(DH)

3-Phase
Only

GRA(Y2)

A09071

Fig. 9 -- High-- and Control--Voltage Connections

4. Connect field L1 to black wire on connection 11 of the

compressor contactor.

5. Connect field wire L2 to yellow wire on connection 23 of

the compressor contactor.

Three--phase units:

1. Run the high--voltage (L1, L2, L3) and ground lead into the

control box.

2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side

of the contactor.

4. Connect field L1 to black wire on connection 11 of the

compressor contactor.

5. Connect field wire L3 to yellow wire on connection 13 of

the compressor contactor.

6. Connect field wire L2 to blue wire from compressor.

604D

--

--

A