beautypg.com

Warning – Bryant 604D--A User Manual

Page 3

background image

3

under a partial overhang (such as a normal house overhang) is 48
in. (1219 mm) above the unit top. The maximum horizontal

extension of a partial overhang must not exceed 48 in. (1219 mm).
IMPORTANT: Do not restrict outdoor airflow. An air restriction
at either the outdoor--air inlet or the fan discharge may be
detrimental to compressor life.
Do not place the unit where water, ice, or snow from an overhang

or roof will damage or flood the unit. Do not install the unit on
carpeting or other combustible materials. Slab--mounted units

should be at least 4 in. (102 mm) above the highest expected water
and runoff levels. Do not use unit if it has been under water.

Step 4 — Rig and Place Unit

Rigging and handling of this equipment can be hazardous for many

reasons due to the installation location (roofs, elevated structures,

etc.).
Only trained, qualified crane operators and ground support staff

should handle and install this equipment.
When working with this equipment, observe precautions in the

literature, on tags, stickers, and labels attached to the equipment, and

any other safety precautions that might apply.
Training for operators of the lifting equipment should include, but not

be limited to, the following:

1. Application of the lifter to the load, and adjustment of the lifts

to adapt to various sizes or kinds of loads.

2. Instruction in any special operation or precaution.

3. Condition of the load as it relates to operation of the lifting kit,

such as balance, temperature, etc.

Follow all applicable safety codes. Wear safety shoes and work

gloves.

INSPECTION
Prior to initial use, and at monthly intervals, all rigging shackles,

clevis pins, and straps should be visually inspected for any damage,
evidence of wear, structural deformation, or cracks. Particular

attention should be paid to excessive wear at hoist hooking points and

load support areas. Materials showing any kind of wear in these areas
must not be used and should be discarded.

UNIT FALLING HAZARD
Failure to follow this warning could result in personal injury

or death.
Never stand beneath rigged units or lift over people.

!

WARNING

PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal

injury/death or property damage.
When straps are taut, the clevis should be a minimum of 36 in.

(914 mm) above the unit top cover.

!

WARNING

604D

--

--