Two Cooling Fan Speeds Set-up (Dehumidification

feature used)

IMPORTANT: Dehumidification control must open control
circuit on humidity rise above set point.
Use of the dehumidification cooling fan speed requires use of
either a 24 VAC dehumidistat or a thermostat which includes

control of a 24 VAC dehumidistat connection. In either case, the

dehumidification control must open the control circuit on humidity
rise above the dehumidification set point. Dehumidification

controls are available with the reverse logic; these must not be
used.

1. Using Fig. 15, move the two pin DEHUM jumper from the

“STD” position to the “DEHUM” position.

2. Remove fan speed tap wire from the “LOW” terminal on

the interface fan board (IFB) (See Fig. 15).

3. Determine correct normal cooling fan speed for unit and

application. Add the wet coil pressure drop in Table 5 to
the system static to determine the correct cooling airflow

speed in Table 4 that will deliver the nominal cooling
airflow as listed in Table 1 for each size.
NOTE: If accessory electric heat is installed, the dry
airflow must meet or exceed the minimum airflow speed
specified in Table 2 for the specific size unit. The electric
heat fan speed will be the same as the normal cooling fan
speed.

4. Remove the vinyl cap off of the desired speed tap wire

(Refer to Table 3 for color coding) for the normal cooling
fan speed and place desired speed tap wire on “HIGH” on

the interface board.

5. Refer to airflow tables (Table 4) to determine allowable

speeds for the dehumidification cooling fan speed. In Table

4, speeds that are not allowed for dehumidification cooling
are shaded.

6. Remove the vinyl cap off of the desired speed tap wire

(Refer to Table 3 for color coding) for the dehumidification
cooling fan speed and place desired speed tap wire on the

“LOW” connection on the interface board (IFB). Verify
that static pressure is in the acceptable range for the speed

tap to be used for dehumidification cooling.

7. Use any spare vinyl plugs to cap any unused speed tap

wires.

Table 3 – Color Coding for Indoor Fan Motor Leads

Black = High Speed

Orange = Med--High Speed

Red = Med Speed

Pink = Med--Low Speed

Blue = Low Speed

Single Speed Cooling With Higher Electric Heat Speed

This unit can also be configured to operate with single speed
cooling and a higher speed for an accessory electric heater.

1. Using Fig. 15, move the two pin DEHUM jumper from the

“STD” position to the “DEHUM” position.

2. See Table 2 for minimum airflow for electric heat operation.

Add electric heater and filter pressure drop to duct system

static pressure to determine total external static pressure.

3. Select speed tap from Table 4 that will achieve required

airflow from Table 2.

4. Remove the vinyl cap off of the desired speed tap wire

(Refer to Table 3 for color coding).

5. Connect the desired speed tap wire to the “HIGH” terminal

on the interface fan board (IFB).

UNIT OPERATION HAZARD

Failure to follow this caution may result in unit component

damage or improper operation.
To use this mode, a speed connection must be made on the

“HIGH” terminal that meets or exceeds the minimum

airflow found in Table 2.

!

CAUTION

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Disconnect electrical power to the unit and install lockout

tag before changing blower speed.

!

WARNING

Continuous Fan Operation

When the DEHUM feature is not used, the continuous fan speed

will be the same as cooling fan speed. When the DEHUM feature
is used, the continuous fan will operate on IFB “LOW” speed

when the DH control lead is not energized, or IFB “HIGH” speed
when the DH lead is energized (see Fig. 15).