B. Trouble shooting problems where a soft lockout code is displayed. When a soft lockout occurs, the boiler will

shut down and the display will alternate between the number “9” and the letter “b” followed by a two digit

service code. The boiler will automatically restart once the condition that caused the lockout is corrected.

CODE

CONDITION

POSSIBLE CAUSES

b 08

Pressure switch circuit open

• Blockage in intake or vent system.

• Vent and/or intake system not constructed in accordance

with Part VI.

• Blocked or leaking pressure switch tubing

• Heat exchanger or burner blockage

• Terminals exposed to high winds

• Blockage in condensate trap above vent.

b 18

MCBA supply sensor detected temperatures in excess

of 200°F

• Heating load at time of error was far below the minimum

firing rate of the boiler

• Defective primary pump or no flow in primary loop (Piping

Method 1)

• Control system miswired so that boiler operation is

permitted when no zones are calling

b 19

MCBA return sensor detected temperatures in excess of

200°F

• See possible causes for “b18”

• Flow through boiler reversed

• Sensor wiring reversed

b 24

MCBA is reading a return sensor temperature higher

than the supply sensor temperature. Condition must be

present for at least 75s for this error code to appear.

• Flow through boiler reversed. Verify correct piping and

pump orientation.

• No boiler water flow. Verify that system is purged of air

and that appropriate valves are open.

• Sensor wiring reversed.

• Supply or return sensor defective.

b 25

Supply water temperature has risen too quickly

• See possible causes for “b18”

• Inadequate boiler water flow. Verify that pump is

operating and that pump and piping are sized per Part

VIII of this manual

b 26

Boiler safety limit, or external limit wired across terminals

3&4, is open.

• See possible causes for “b18”

• Defective supply sensor.

b 30

Temperature rise between supply and return is too high.

• Inadequate boiler water flow. Verify that pump is

operating and that pump and piping are sized per Part

VIII of this manual

b 61

Pressure switch circuit closed with fan off

• Blockage in pressure switch hose

• Pressure switch wires shorted together

• Defective pressure switch

• Loose or miswired fan speed harness (if “b61” error code

is observed while fan is running)

b 65

Fan is not achieving set point speed

• Loose or incorrect fan speed control connection

• Defective fan

Table 13.3: Soft Lockout Codes Displayed