11 table 6.2b: summary of vertical venting options – Burnham CHG225 User Manual
Page 11

11
Table 6.2b: Summary of Vertical Venting Options
VENT OPTION #
6
7
CLASSIFICATION USED IN THIS
MANUAL
VERTICAL
DIRECT VENT
VERTICAL
DIRECT VENT
ILLUSTRATED IN FIGURE
6.4
6.4
VENT PIPE STRUCTURE
PENETRATION
ROOF
ROOF
AIR INTAKE PIPE STRUCTURE
PENETRATION
ROOF
ROOF
VENT PIPE SIZE
3”
4”
AIR INTAKE PIPE SIZE
4”
4”
MAXIMUM
VENT
PIPE
LENGTH
CHG150
49.5 FT
N.R.
CHG225
N.R.
47 FT
MAXIMUM INT
AKE
PIPE LENGTH
CHG150
52 FT
N.R.
CHG225
N.R.
52 FT
EXHAUST TERMINAL
RODENT SCREEN BY VENT SYSTEM
MANUFACTURER. SAME DIAMETER
AS VENT SYSTEM. SEE TABLE 6.5.
AIR INTAKE TERMINAL
4” 180 ELBOW
4” 180 ELBOW
VENT MATERIAL
APPROVED VENT SYSTEM SHOWN
IN TABLE 6.5
AIR INTAKE MATERIAL
GALVANIZED OR PVC
“N.R” - Not recommended “N.A.” - Not applicable