11 table 6.2b: summary of vertical venting options – Burnham CHG225 User Manual

Page 11

background image

11

Table 6.2b: Summary of Vertical Venting Options

VENT OPTION #

6

7

CLASSIFICATION USED IN THIS

MANUAL

VERTICAL

DIRECT VENT

VERTICAL

DIRECT VENT

ILLUSTRATED IN FIGURE

6.4

6.4

VENT PIPE STRUCTURE

PENETRATION

ROOF

ROOF

AIR INTAKE PIPE STRUCTURE

PENETRATION

ROOF

ROOF

VENT PIPE SIZE

3”

4”

AIR INTAKE PIPE SIZE

4”

4”

MAXIMUM

VENT

PIPE

LENGTH

CHG150

49.5 FT

N.R.

CHG225

N.R.

47 FT

MAXIMUM INT

AKE

PIPE LENGTH

CHG150

52 FT

N.R.

CHG225

N.R.

52 FT

EXHAUST TERMINAL

RODENT SCREEN BY VENT SYSTEM

MANUFACTURER. SAME DIAMETER

AS VENT SYSTEM. SEE TABLE 6.5.

AIR INTAKE TERMINAL

4” 180 ELBOW

4” 180 ELBOW

VENT MATERIAL

APPROVED VENT SYSTEM SHOWN

IN TABLE 6.5

AIR INTAKE MATERIAL

GALVANIZED OR PVC

“N.R” - Not recommended “N.A.” - Not applicable