3) Two basic types of errors codes are shown on the display:

• Soft Lockout Codes – When a soft lockout occurs, the boiler will shut down and the display will alternate

between the number “9” and the letter “b” followed by a two digit service code. A list of these

codes, and their meanings, is shown in Table 13.3. The boiler will automatically restart once the condition that

caused the lockout is corrected.

• Hard Lockout Codes – When a hard lockout occurs, the boiler will shut down and the display will

flash the letter “E” followed by a two digit service code. A list of these codes, and their meanings, is

shown in Table 13.4. Once the condition that caused the lockout is corrected, the boiler will need to be

manually reset using the RESET button on the display.

4) If an outdoor sensor is installed, the boiler will automatically adjust the heating zone set point temperature

based on the outdoor reset curve in Figure 11.4. The maximum set point is defined by parameter 4 (factory set

to 180°F) when the outdoor temperature is 0°F or below. The minimum set point temperature shown is 100°F

when the outdoor temperature is 60°F or above. As the outdoor temperature falls the supply water target

temperature increases. For example, if the outdoor air temperature is 30°F, the set point temperature for the

supply water is 140°F.

5) An indirect water heater thermostat can be connected between terminals 7 and 8 on the terminal strip. When

this thermostat closes, the central heating circulator will be turned off and the DHW circulator will be turned

on.

6) An external limit control can be installed between terminals 3 and 4 on the terminal strip. Be sure to remove

the jumper between terminals 3 and 4 when adding an external limit control to the system. If the external limit

opens, the boiler will shut down and error code “b 26” will be displayed. If the limit installed is a manual

reset type, it will need to be reset before the boiler will operate.

Table 11.3: Boiler Status Codes

First Digit

Boiler Status

0

Burner off - No call for heat or DHW

1

Pre-purge or post-purge

2

Ignition

3

Burner responding to call for heat

4

Burner responding to call for DHW

5

Checking air pressure switch

6

Burner off - Set point temperature has been reached

7

Call for heat ended. 10s heating post pump period

8

Call for DHW ended. 10s DHW post pump period

9 and b

Flashing

Burner off - on soft lockout. See Troubleshooting

Section to determine meaning of error code.

A

Boiler responding to call from heating zone

H

Burner on - Held in high fire

L

Burner on - Held in low fire