• Air intake terminal must not terminate in areas that might contain combustion air contaminates, such as near

swimming pools. See Section IV for more information on possible contaminates.

6) Permitted Terminals for Vertical Venting (Vent Options 6, 7) - A rodent screen is installed in the end of the vent

pipe. Vent manufacturer part numbers for these screens are shown in Table 4. The air inlet terminal consists of a 180

degree elbow (or two 90 degree elbows) with a rodent screen as shown in Figure 6.4.

7) Vertical Vent Terminal Locations (Vent Options 6,7) - Observe the following limitations on the location of all

vertical vent terminals (see Figure 6.4):
• The top of the vent pipe must be at least 2 feet above any object located within 10 feet.
• The vertical distance between top of the vent and air inlet terminal openings must be at least 12”.
• The bottom of the air inlet terminal must be at least 12” above the normal snow accumulation that can be

expected on the roof.

• The air intake terminal must be located on the roof and must be no further than 24” horizontally from the exhaust

pipe.

8) Wall thimbles – Wall thimbles are required where the vent pipe passes through combustible walls with less than the

required clearance shown in Table 4.2 or as required by local codes. Vent manufacturer’s wall thimble part numbers

are shown in Table 6.5.

9) Pitch of Horizontal piping – All horizontal vent piping must be pitched ¼” per foot so that any condensate which

forms in this piping will run towards the boiler.

10) Vertical and horizontal sections of piping must be properly supported. See vent system manufacturer’s instructions

for more information.

11) Fire Stops – Use fire stops where required by code or by the vent system manufacturer. Consult vent system

manufacturer’s literature for information on suitable fire stops.

Figure 6.4: Vertical Vent System (Vent Options 6,7)