beautypg.com

Bryant Series B 345MAV User Manual

Page 37

background image

b. Remove cap that conceals adjustment screw for gas

valve regulator. (See Fig. 40.)

c. Turn adjusting screw, counterclockwise (out) to decrease

manifold pressure or clockwise (in) to increase manifold
pressure.

NOTE:

This furnace has been approved for a manifold pressure

of 3.2 in. wc to 3.8 in. wc when installed at altitudes up to 2000 ft.
For altitudes above 2000 ft, the manifold pressure can be adjusted
from 2.0 in. wc to 3.8 in. wc.

CAUTION:

DO NOT bottom out gas valve regulator

adjusting screw. This can result in unregulated manifold
pressure and result in excess overfire and heat exchanger
failures.

NOTE:

If orifice hole appears damaged or it is suspected to have

been redrilled, check orifice hole with a numbered drill bit of
correct size. Never redrill an orifice. A burr-free and squarely
aligned orifice hole is essential for proper flame characteristics.

d. Replace gas valve regulator adjustment screw cap.

e. Replace burner enclosure front and verify adjusted gas

input rate using method outlined in item 3.

f. Look through sight glass in burner enclosure and check

burner flame. Burner flame should be clear blue, almost
transparent. (See Fig. 41.)

3. Verify natural gas input rate by clocking gas meter.

NOTE:

Be sure all pressure tubing, combustion-air and vent

pipes, and burner enclosure front are in place when checking input
by clocking gas meter.

NOTE:

High-Altitude Adjustment

UNITED STATES

At altitudes above 2000 ft, this furnace has been approved for a 2%
derate for each 1000 ft above sea level. See Table 8 for derate
multiplier factor.

EXAMPLE:
100,000 Btuh input furnace installed at 4300 ft.

Furnace Input Rate

at Sea Level

X

Derate

Multiplier

Factor

=

Furnace Input Rate

at Installation

Altitude

100,000

X

0.91

=

91,000

CANADA

At installation altitudes from 2000 to 4500 ft, this furnace must be
derated 5% by an authorized Gas Conversion Station. To deter-
mine correct input rate for altitude, see example above and use
0.95 as derate multiplier factor.

a. Turn off all other gas appliances and pilots.

b. Start furnace and let operate for 3 minutes.

Fig. 40—Redundant Automatic Gas Valve

A95622

MANIFOLD
PRESSURE TAP

GAS
PRESSURE
REGULATOR
ADJUSTMENT

BURNER
ENCLOSURE
REFERENCE
PRESSURE
TAP

INLET
PRESSURE TAP

ON AND
OFF SWITCH

CAUTION:

DO NOT redrill orifices. Improper drilling

(burrs, out-of-round holes, etc.) can cause excessive
burner noise and misdirection of burner flames. This can
result in flame impingement of burners and heat exchang-
ers causing failures.

A93059

BURNER

ORIFICE

Fig. 41—Burner Flame

A89020

BURNER FLAME

BURNER

MANIFOLD

TABLE 8—ALTITUDE DERATE MULTIPLIER FOR U.S.A.

ALTITUDE

(FT)

% OF

DERATE

DERATE MULTIPLIER

FACTOR FOR U.S.A*

0—2000

0

1.00

2001—3000

4—6

0.95

3001—4000

6—8

0.93

4001—5000

8—10

0.91

5001—6000

10—12

0.89

6001—7000

12—14

0.87

7001—8000

14—16

0.85

8001—9000

16—18

0.83

9001—10,000

18—20

0.81

* Derate multiplier factor is based on midpoint altitude for altitude range.

—37—