CAUTION:

Do not use this furnace during construction

when adhesives, sealers, and/or new carpets are being
installed and curing. If the furnace is required during
construction, use clean outside air for combustion and
ventilation. Compounds of chlorine and fluorine, when
burned with combustion air, form acids which will cause
corrosion of heat exchangers. Some of these compounds
are released from paneling and dry wall adhesives, paints,
thinners, masonry cleaning materials, and many other
solvents commonly used in the construction process.
Excessive exposure to contaminated combustion air will
result in safety and performance related problems.

II.

FURNACE

LOCATION

RELATIVE

TO

COOLING

EQUIPMENT

The cooling coil must be installed parallel with or on downstream
side of furnace to avoid condensation in heat exchanger. When
installed parallel with a furnace, dampers or other means used to
control flow of air must prevent chilled air from entering furnace.
If dampers are manually operated, they must be equipped with a
means to prevent operation of either unit unless damper is in
full-heat or full-cool position.

NOTE:

These furnaces are designed for a minimum continuous

return-air temperature of 60°F or intermittent operation down to 55°F
such as when used with a night setback thermostat. Return-air
temperature must not exceed a maximum of 85°F. Failure to follow
these return-air temperature limits may affect reliability of heat
exchangers, motors, and controls.

A93042

FRONT

RETURN
AIR

MAX 85°F

MIN 55°F

°F

°F

WARNING:

Do not install furnace on its back. Safety

control operation will be adversely affected. Never con-
nect return-air ducts to back of furnace. Failure to follow
this warning could result in fire, personal injury, or death.

A93043

FRONT

BACK

FRONT

B
A
C
K

CAUTION:

If these furnaces are installed in an uncon-

ditioned space where ambient temperatures may be 32°F
or lower, freeze protection measures must be taken.

A93058

32

°

F MINIMUM INSTALLED

AMBIENT OR FREEZE
PROTECTION REQUIRED

—12—