H.

Condensate Trap Freeze Protection

Refer to Condensate Drain Protection section for recommenda-
tions and procedures.

III.

DOWNFLOW APPLICATIONS

A downflow furnace application is where furnace blower is located
above combustion and controls section of furnace, and conditioned
air is discharged downwards.

A.

Condensate Trap Location

The condensate trap must be removed from the factory-installed
blower shelf location and relocated in selected application location
as shown in Fig. 2, 8, or 9.

To relocate condensate trap from the blower shelf to desired
location, perform the following:

1. Remove 3 tubes connected to condensate trap.

2. Remove trap from blower shelf by gently pushing tabs

inward and rotating trap.

3. Install casing hole filler cap (factory-supplied in loose parts

bag) into blower shelf hole where trap was removed.

WARNING:

Casing hole filler cap must be installed in

blower shelf when condensate trap is relocated. Failure to
follow this warning could result in electrical shock, fire,
personal injury or death.

4. Install condensate trap into left-hand side casing hole by

inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.

5. Fill unused condensate trap casing holes with plastic filler

caps (factory-supplied in loose parts bag).

B.

Condensate Trap Tubing

NOTE:

See Fig. 8 or 9 or tube routing label on main furnace door

to check for proper connections.

1. Collector Box Drain Tube

a. Remove factory-installed plug from LOWER collector

box drain tube (blue and white striped label).

b. Install removed clamp and plug into UPPER collector

box drain tube (blue label) which was connected to
condensate trap.

c. Connect LOWER collector box drain connection to

condensate trap.

(1.) Condensate Trap Located on Left Side of Casing

(a.) Connect LOWER collector box drain tube

(blue and white striped label) to condensate
trap. Tube does not need to be cut.

(b.) Clamp tube to prevent any condensate leakage.

(2.) Condensate Trap Located on Right Side of Casing

(a.) Install drain tube coupling (factory-supplied in

loose parts bag) into collector box drain tube
(blue and white striped label) which was pre-
viously plugged.

(b.) Connect larger diameter drain tube (factory-

supplied in loose parts bag) to drain tube
coupling, extending collector box drain tube
for connection to condensate trap.

(c.) Route extended collector box drain tube di-

rectly from collector box drain to condensate
trap as shown in Fig. 9.

(d.) Determine appropriate length and cut.

(e.) Connect to condensate trap.

(f.) Clamp tube to prevent any condensate leakage.

2. Inducer Housing Drain Tube

Fig. 8—Downflow Tube Configuration

(Left-Hand Trap Installation)

A00262

PLUG

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

DRAIN TUBE (BLUE

& WHITE STRIPED)

COLLECTOR BOX
EXTENSION TUBE

CONDENSATE

TRAP

INDUCER HOUSING

DRAIN TUBE (VIOLET)

COLLECTOR BOX

EXTENSION TUBE

CAP

COLLECTOR BOX

DRAIN TUBE (BLUE)

Fig. 9—Downflow Tube Configuration

(Right-Hand Trap Installation)

A00296

PLUG

COLLECTOR BOX
TUBE (GREEN)

COLLECTOR BOX
TUBE (PINK)

COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)

COLLECTOR BOX
EXTENSION
DRAIN TUBE

CONDENSATE
TRAP

INDUCER HOUSING
DRAIN TUBE
(VIOLET)

COLLECTOR BOX
EXTENSION TUBE

DRAIN TUBE
COUPLING

COLLECTOR BOX
DRAIN TUBE (BLUE)

CAP

COLLECTOR BOX
EXTENSION TUBE

—8—