AIR DELIVERY -- CFM (WITH FILTER)*

UNIT SIZE

RETURN---AIR

SUPPLY

SPEED

EXTERNAL STATIC PRESSURE (in. wc)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

024045

Bottom or

Side(s)

5

1185

1145

1115

1075

1035

980

905

820

720

580

4

920

880

835

800

755

720

680

645

605

540

3

735

685

625

585

530

490

435

395

345

295

2

820

765

725

670

630

580

545

490

455

405

1

650

595

535

490

430

390

330

280

235

--- ---

048070

Bottom or

Side(s)

5

1625

1585

1535

1495

1460

1415

1365

1295

1220

1125

4

1405

1360

1320

1280

1240

1195

1155

1115

1070

1030

3

1240

1200

1155

1110

1065

1020

975

935

895

850

2

1190

1140

1095

1050

1000

955

915

870

830

790

1

1035

985

930

885

835

785

745

695

650

600

048090

Bottom or

Side(s)

5

1845

1800

1755

1710

1665

1595

1500

1400

1275

1105

4

1590

1545

1500

1455

1410

1365

1315

1270

1180

1000

3

1365

1320

1270

1215

1170

1125

1070

1025

955

900

2

1225

1160

1110

1060

1010

950

895

830

770

710

1

1100

1030

960

875

805

730

645

570

505

425

060110

Bottom or

Side(s)

5

2255

2205

2150

2100

2040

1985

1920

1835

1735

1615

4

1600

1525

1465

1400

1335

1275

1210

1150

1080

1015

3

1945

1890

1830

1770

1715

1655

1600

1545

1480

1430

2

1420

1340

1280

1200

1140

1065

1005

925

865

790

1

1280

1205

1140

1055

990

910

840

760

695

630

060135

Bottom or

Side(s)

5

2295

2240

2185

2125

2070

2005

1925

1805

1670

1545

4

1725

1660

1605

1545

1460

1395

1340

1285

1230

1170

3

1910

1865

1800

1745

1685

1610

1545

1485

1435

1380

2

1630

1575

1510

1435

1365

1300

1245

1185

1130

1065

1

1430

1355

1285

1200

1125

1075

1015

945

855

800

*A filter is required for each return---air inlet. Airflow performance included 3/4---in. (19 mm) washable filter media such as contained in factory---authorized ac-

cessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.

--- --- Indicates unstable operating conditions.

ELECTRICAL DATA

313AAV/

JAV UNIT

SIZE

VOLTS---

HERTZ---

PHASE

OPERATING VOLTAGE

RANGE

*

MAXIMUM

UNIT AMPS

MAXIMUM WIRE

LENGTH FT (M)

}

MAXIMUM FUSE

OR CKT BKR

AMPS

{

MINIMUM

WIRE GAGE

Maximum

Minimum

024045

115---60---1

127

104

8.1

34 (10)

15

14

048070

115---60---1

127

104

9.5

29 (9)

15

14

048090

115---60---1

127

104

10.3

27 (8)

15

14

060110

115---60---1

127

104

13.1

34 (10)

20

12

060135

115---60---1

127

104

13.1

34 (10)

20

12

* Permissible limits of the voltage range at which the unit operates satisfactorily.
{

Time---delay type is recommended.

}

Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.