beautypg.com

Guide specifications, General, Products – Bryant 313AAV/JAV User Manual

Page 12

background image

12

GUIDE SPECIFICATIONS

Gas Furnace
313AAV/JAV

GENERAL

System Description

Furnish a _________________ fixed capacity gas--fired furnace

for use with natural gas or propane (factory authorized conversion
kit required for propane); furnish cold air return plenum; furnish

external medial cabinet for use with accessory media filter or
standard filter.

Quality Assurance

Unit will be designed, tested and constructed to the current ANSI Z

21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will be 3rd party certified by CSA to the current ANSI Z

21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will carry the CSA Blue Star® and Blue Flame® labels.
Unit efficiency testing will be performed per the current DOE test

procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the

latest GAMA Consumer’s Directory of Certified Efficiency
Ratings.
Unit will carry the current Federal Trade Commission Energy

Guide efficiency label.

Delivery, Storage and Handling

Unit shall be shipped as single package only and is stored and

handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only. Warranty certificate available upon request.

PRODUCTS

Equipment

Components shall include: slow--opening gas valve to reduce

ignition noise, regulate gas flow, with electric switch gas shut--off;

flame proving sensor, hot surface igniter, pressure switch assembly;
flame rollout switch, blower and inducer assembly, 40va

transformer; low--voltage (heating) (heating/ cooling) thermostat.

Blower Wheel and Blower Motor

Galvanized blower wheel shall be centrifugal type, statically and
dynamically balanced. Blower motor of ECM type shall be

permanently lubricated with sealed bearings, of _______hp, and
shall be multiple--speed direct drive. Blower motor shall be soft

mounted to the blower scroll to reduce vibration transmission.

Filters

Furnace may have reusable--type filters. Filter shall be _______ in
(x) _______in. (mm).An accessory high efficiency Media Filter is

available as an option. _______________ Media Filter.

Casing

Casing shall be of .030 in. (.76 mm) thickness minimum,

pre--painted galvanized steel.

Inducer Motor

Inducer motor shall be soft mounted to reduce vibration

transmission.

Draft Safeguard Switch

Draft Safeguard Switch (blocked vent safeguard) shall be factory
installed to reduce the possibility of vent gas infiltration due to a

blocked or restricted vent pipe.

Heat Exchangers

Heat exchangers shall be a 4--Pass 20 gage aluminized steel of
fold--and--crimp sectional design when applied operating under

negative pressure.

Controls

Control shall include a micro--processor based integrated electronic
control board with at least 11 service troubleshooting codes

displayed via diagnostic flashing LED light on the control, a
self--test feature that checks all major functions of the furnace

within one minute, and a replaceable automotive--type circuit
protection fuse. Multiple operational settings available including,

separate blower speeds for heating, cooling and continuous fan.

Continuous fan speed may be adjusted from the thermostat.
Features will also include temporary reduced airflow in the cooling

mode for improved dehumidification when a Thermidistatt
Control is selected as the thermostat.

Operating Characteristics

Heating Capacity shall be ________ Btuh input; ________ Btuh

output capacity.
Fuel Gas Efficiency shall be 80% AFUE.
Air delivery shall be ___________ CFM minimum at 0.50 in. wc

external static pressure.
Dimensions shall be: depth __________ in.; width _________ in;

height_________in.

(mm)

(casing

only).

Height

shall

be_________in. (mm) with A/C coil and _____________in. (mm)

overall with plenum.

Electrical Requirements

Electrical supply shall be 115 volts, 60 Hz, single--phase (nominal).
Minimum wire size shall be_________AWG; maximum fuse size

or circuit breaker shall be __________Amps.

Special Features

Refer to section of the product data sheet identifying accessories
and descriptions for specific features and available enhancements.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

8 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231

Printed in U.S.A.

Edition Date: 3/09

Replaces: PDS313AAV--- 03

Catalog No. PDS313AAV---04

313AA

V/

JA

V