beautypg.com

Bryant LOW-BOY 367AAN User Manual

Page 3

background image

The air handling capacity of this furnace is designed for cooling
airflow. Refer to Table 7 for expected airflows at various external
duct static pressures.

LOCATION

I.

GENERAL

WARNING:

This furnace is not water tight and is not

designed for outdoor installation. This furnace shall be
installed in such a manner as to protect electrical com-
ponents from water. Outdoor installation would lead to a
hazardous electrical condition and to premature furnace
failure.

WARNING:

Do not use this furnace as a construction

heater. Use of this furnace as a construction heater
exposes furnace to abnormal conditions, contaminated
combustion air, and lack of air filters. Failure to follow
this warning can lead to premature furnace failure and/or
vent failure which could result in a fire hazard and/or
bodily harm.

This furnace is approved for reduced clearances to combustible
construction, therefore, it may be installed in a closet or similar
enclosure. It may be located in a basement or on the same level as
area to be heated. In any case, unit should always be installed level.

The required minimum clearances for this furnace are specified in
Table 1.

The furnace should be located as close as possible to chimney or
vent in order to keep vent connections short and direct. The
furnace should also be located as near as possible to center of air
distribution system.

II.

LOCATION RELATIVE TO COOLING EQUIPMENT

When installing furnace with cooling equipment for year-round
operation, the following recommendations must be followed for
series or parallel airflow:

1. In series airflow applications, coil is mounted after furnace

in an enclosure in supply-air stream. The furnace blower is
used for both heating and cooling airflow.

WARNING:

The coil MUST be installed on air dis-

charge side of furnace. Under no circumstances should
airflow be such that cooled, conditioned air can pass over
furnace heat exchanger. This will cause condensation in
heat exchanger and possible failure of heat exchanger
which could lead to a fire hazard and/or a hazardous
condition which may lead to bodily harm. Heat exchanger
failure due to improper installation may not be covered by
warranty.

2. In parallel airflow applications, dampers must be provided

to direct air over furnace heat exchanger when heat is
desired and over cooling coil when cooling is desired.

IMPORTANT:

The dampers should be adequate to prevent

cooled air from entering furnace. If manually operated, dampers
must be equipped with a means to prevent operation of either
cooling unit or furnace unless damper is in full cool or heat
position.

AIR FOR COMBUSTION AND VENTILATION

WARNING:

Installation of this furnace in an area where

it will receive contaminated combustion air must be
avoided. Such contamination would include the follow-
ing: ammonia, chlorine, hydrogen sulfide, halogenated
hydrocarbons, carbon tetrachloride, cleaning solvents,
hydrochloric acid, water softening chemicals, and similar
chemicals. Failure to follow this warning will lead to
premature rusting of heat exchanger and possible prema-
ture furnace failure and/or vent failure which could result
in fire hazard and/or bodily harm.

WARNING:

Do not block combustion-air openings in

the furnace. Any blockage will result in improper com-
bustion which may result in a fire hazard and/or cause
bodily harm.

I.

GENERAL

This furnace should be installed in a location in which facilities for
ventilation permit satisfactory combustion of oil, proper venting,
and maintenance of ambient temperature at safe limits under
normal conditions of use. The location should not interfere with
proper circulation of air within the confined space. (See NFPA-31,
Section 1.5.)

In addition to air needed for combustion, process air shall be
provided as required for: cooling of equipment or material,
controlling dew point, heating, drying, oxidation or dilution, safety
exhaust, and odor control.

In addition to air needed for combustion, air shall be supplied for
ventilation, including all air required for comfort and proper
working conditions for personnel.

The barometric draft regulator (included with furnace) shall be
installed in same room or enclosure as furnace in such a manner as
to prevent any difference in pressure between regulator and
combustion-air supply.

Air requirements for operation of exhaust fans, kitchen ventilation
systems, clothes dryers, and fireplaces shall be considered in
determining the adequacy of a space to provide combustion-air
requirements.

The lack of a proper amount of combustion air can lead to serious
furnace operational problems. Some of these problems are:

1. Excessive oil burner after drip and oil fumes.

TABLE 1—MINIMUM CLEARANCES TO

COMBUSTIBLE MATERIALS (IN.)

UNIT APPLICATION

LOW-BOY

Sides

Furnace

1

Supply Plenum and Warm-Air Duct Within 6 ft
of Furnace

1

Back

Service Clearance

19

Top

Furnace Casing or Plenum

2

Horizontal Warm-Air Duct Within 6 ft of
Furnace

2

Bottom*

0

Flue
Pipe

Horizontally or Below Pipe

4

Vertically Above Pipe

9

Front

8

* Floor may be combustible.
NOTE: Adequate service clearance should be provided over and above these

dimensions as required.

—3—